The Definitive Guide toAI Data Centers
Ask the GuideAboutAccount

Library

Read these too

This guide connects the disciplines; it does not replace the specialist references. The committee standards own the classes and requirements you certify against, the OEM documentation governs the build once a platform is chosen, the institutions and analysts produce the measurements and forecasts the register cites. For every entry below: what it is authoritative for, and the moment to leave this site and open it. Document identities below come from Appendix A, with an edition, dated publication status and applicable boundary. Access for the other references was checked 2026-09-05; paid does not mean avoidable.

facility requirements

Choose the applicable document and edition before writing acceptance criteria. Publication status does not establish local adoption or product compliance.

TIA

Document: standard · C (2024)

Status: current · as of

Publication record ↗

Authoritative for: Facility infrastructure and Rated levels.

Reach for it when: Specifying or checking requirements within this document’s boundary.

ANSI/TIA-942-C AI addendum ↗Access terms not published
TIA

Document: standard · Addendum 1; project

Status: draft · as of

Authoritative for: AI facility cabling, power and cooling.

Reach for it when: Specifying or checking requirements within this document’s boundary.

BICSI

Document: standard · 2024

Status: current · as of

Authoritative for: Facility design.

Reach for it when: Specifying or checking requirements within this document’s boundary.

BICSI

Document: standard · 2024

Status: current · as of

Authoritative for: Facility operations.

Reach for it when: Specifying or checking requirements within this document’s boundary.

Uptime Institute

Document: standard · edition not stated online

Status: current · as of

Authoritative for: Facility topology outcomes.

Reach for it when: Specifying or checking requirements within this document’s boundary.

Uptime Institute

Document: standard · effective 2013-04-01

Status: current · as of

Authoritative for: Facility management behaviors.

Reach for it when: Specifying or checking requirements within this document’s boundary.

CENELEC / BSI

Document: standard · 2019

Status: current · as of

Authoritative for: Facility classification.

Reach for it when: Specifying or checking requirements within this document’s boundary.

CENELEC / BSI

Document: standard · 2023

Status: current · as of

Authoritative for: Telecom cabling.

Reach for it when: Specifying or checking requirements within this document’s boundary.

CENELEC / BSI

Document: standard · 2026

Status: current · as of

Authoritative for: Management and operation.

Reach for it when: Specifying or checking requirements within this document’s boundary.

ISO/IEC

Document: standard · 2021

Status: current · as of

Authoritative for: Facility classification.

Reach for it when: Specifying or checking requirements within this document’s boundary.

ISO/IEC

Document: standard · 2024

Status: current · as of

Authoritative for: Building construction.

Reach for it when: Specifying or checking requirements within this document’s boundary.

ISO/IEC

Document: standard · 2021

Status: current · as of

Authoritative for: Power distribution.

Reach for it when: Specifying or checking requirements within this document’s boundary.

ISO/IEC

Document: standard · 2021

Status: current · as of

Authoritative for: Environmental control.

Reach for it when: Specifying or checking requirements within this document’s boundary.

ISO/IEC

Document: specification · 2018

Status: current · as of

Authoritative for: Telecom cabling.

Reach for it when: Specifying or checking requirements within this document’s boundary.

ISO/IEC

Document: standard · 2024

Status: current · as of

Authoritative for: Physical security.

Reach for it when: Specifying or checking requirements within this document’s boundary.

ISO/IEC

Document: specification · 2018

Status: current · as of

Authoritative for: Management and operation.

Reach for it when: Specifying or checking requirements within this document’s boundary.

CENELEC / BSI

Document: standard · 2021

Status: current · as of

Authoritative for: Building construction.

Reach for it when: Specifying or checking requirements within this document’s boundary.

CENELEC / BSI

Document: standard · 2019

Status: current · as of

Authoritative for: Power supply and distribution.

Reach for it when: Specifying or checking requirements within this document’s boundary.

CENELEC / BSI

Document: standard · 2019

Status: current · as of

Authoritative for: Environmental control.

Reach for it when: Specifying or checking requirements within this document’s boundary.

CENELEC / BSI

Document: standard · 2021

Status: current · as of

Authoritative for: Physical security.

Reach for it when: Specifying or checking requirements within this document’s boundary.

thermal references

Choose the applicable document and edition before writing acceptance criteria. Publication status does not establish local adoption or product compliance.

ASHRAE

Document: guideline · Online; revision ID not published

Status: current · as of

Authoritative for: Datacom engineering reference.

Reach for it when: Specifying or checking requirements within this document’s boundary.

ASHRAE

Document: standard · 2025

Status: current · as of

Authoritative for: Data-center energy performance.

Reach for it when: Specifying or checking requirements within this document’s boundary.

ASHRAE

Document: standard · 2020

Status: current · as of

Authoritative for: Cooling-equipment rating tests.

Reach for it when: Specifying or checking requirements within this document’s boundary.

ASHRAE

Document: standard · 2021

Status: current · as of

Authoritative for: Building-water Legionella risk.

Reach for it when: Specifying or checking requirements within this document’s boundary.

ASHRAE

Document: standard · 2024

Status: current · as of

Authoritative for: Building commissioning process.

Reach for it when: Specifying or checking requirements within this document’s boundary.

PNNL / ASHRAE / NEMA

Document: guideline · Online; revision ID not published

Status: current · as of

Authoritative for: AI facility energy and water practices.

Reach for it when: Specifying or checking requirements within this document’s boundary.

ASHRAE

Document: guideline · 2019

Status: current · as of

Authoritative for: Whole-building commissioning.

Reach for it when: Specifying or checking requirements within this document’s boundary.

ASHRAE

Document: guideline · 2025

Status: current · as of

Authoritative for: HVAC commissioning.

Reach for it when: Specifying or checking requirements within this document’s boundary.

ASHRAE

Document: guideline · 2023

Status: current · as of

Authoritative for: Building-water Legionella management.

Reach for it when: Specifying or checking requirements within this document’s boundary.

ASHRAE

Document: guideline · 2017 SI; Sound and Vibration

Status: historical · as of

Authoritative for: Octave/A-weighting, level summation and propagation; no project noise limits.

Reach for it when: Specifying or checking requirements within this document’s boundary.

installation and safety references

Choose the applicable document and edition before writing acceptance criteria. Publication status does not establish local adoption or product compliance.

NFPA

Document: standard · 2026

Status: current · as of

Authoritative for: Electrical installations.

Reach for it when: Specifying or checking requirements within this document’s boundary.

NFPA

Document: standard · 2027

Status: current · as of

Authoritative for: Electrical work safety.

Reach for it when: Specifying or checking requirements within this document’s boundary.

NFPA

Document: standard · 2024

Status: current · as of

Authoritative for: IT equipment fire protection.

Reach for it when: Specifying or checking requirements within this document’s boundary.

NFPA

Document: standard · 2024

Status: current · as of

Authoritative for: Telecom facility fire protection.

Reach for it when: Specifying or checking requirements within this document’s boundary.

NFPA

Document: standard · 2026

Status: current · as of

Authoritative for: Stationary energy-storage installation.

Reach for it when: Specifying or checking requirements within this document’s boundary.

NFPA

Document: standard · 2025

Status: current · as of

Authoritative for: Emergency and standby power systems.

Reach for it when: Specifying or checking requirements within this document’s boundary.

NFPA

Document: standard · 2026

Status: current · as of

Authoritative for: Lightning-protection installation.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEC

Document: standard · 2009 + AMD1:2021; ed. 7.1

Status: current · as of

Authoritative for: System voltage values.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEC

Document: standard · Series; -1:2022 base

Status: varies by part · as of

Authoritative for: Protection relays.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEC

Document: standard · Series; -1:2021 + COR1:2023 base

Status: varies by part · as of

Authoritative for: Industrial plugs and sockets.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEC

Document: standard · Series; -1:2021 base

Status: varies by part · as of

Authoritative for: Equipment couplers.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEC

Document: standard · Series; -1:2025 base

Status: varies by part · as of

Authoritative for: Low-voltage installations.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEC

Document: standard · 2025; corrected 2026-07

Status: current · as of

Authoritative for: Power-quality measurement.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEC

Document: standard · Series; -1:2020 base

Status: varies by part · as of

Authoritative for: Low-voltage assemblies.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEC

Document: standard · 2010; ed. 2.0

Status: current · as of

Authoritative for: Functional-safety application guidance.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEC

Document: standard · 2026 SER pack; part editions vary

Status: varies by part · as of

Authoritative for: Process safety systems.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEC

Document: standard · Series; -01:2024 base

Status: varies by part · as of

Authoritative for: Surge-protective devices.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEC

Document: standard · 2024; ed. 1.0

Status: current · as of

Authoritative for: Surge-protection general requirements.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEC

Document: standard · 2025; ed. 2.0

Status: current · as of

Authoritative for: AC surge-protective devices.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEC

Document: standard · 2025; ed. 1.0

Status: current · as of

Authoritative for: DC surge-protective devices.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEC

Document: standard · 2026 SER pack; part editions vary

Status: varies by part · as of

Authoritative for: Utility-automation communications.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEC

Document: standard · 2020; ed. 2.0

Status: current · as of

Authoritative for: Static active-energy meters.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEC

Document: standard · 2026 SER pack; part editions vary

Status: varies by part · as of

Authoritative for: High-voltage switchgear.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEC

Document: standard · 2026 SER pack; parts 1–4:2024

Status: varies by part · as of

Authoritative for: Lightning protection.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEC

Document: standard · 2024 + COR1:2024; ed. 3.0

Status: current · as of

Authoritative for: Lightning-risk management.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEC

Document: standard · 2024; ed. 3.0

Status: current · as of

Authoritative for: Physical lightning protection.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEC

Document: standard · 2022; ed. 2.0

Status: current · as of

Authoritative for: Alarm-system management.

Reach for it when: Specifying or checking requirements within this document’s boundary.

CEN / BSI

Document: standard · Series; -1:2021 introduction

Status: varies by part · as of

Authoritative for: Fire detection and alarms.

Reach for it when: Specifying or checking requirements within this document’s boundary.

CEN / BSI

Document: standard · Series; -1:2026 general

Status: varies by part · as of

Authoritative for: Unfired pressure vessels.

Reach for it when: Specifying or checking requirements within this document’s boundary.

CEN / BSI

Document: standard · Series; -1:2024 general

Status: varies by part · as of

Authoritative for: Metallic industrial piping.

Reach for it when: Specifying or checking requirements within this document’s boundary.

CEN / BSI

Document: standard · 2026

Status: current · as of

Authoritative for: Building environmental assessment.

Reach for it when: Specifying or checking requirements within this document’s boundary.

CEN / NSAI

Document: standard · 2017 + A1:2020

Status: current · as of

Authoritative for: Oxygen-reduction fire prevention.

Reach for it when: Specifying or checking requirements within this document’s boundary.

ETSI

Document: standard · V2.1.1 (2012-02); replaced by Part 3 V2.3.1 (2023)

Status: superseded · as of

Authoritative for: DC power interface up to 400 V at telecom/ICT equipment input.

Reach for it when: Specifying or checking requirements within this document’s boundary.

ISO

Document: standard · 2020 + Amd1:2022

Status: current · as of

Authoritative for: Freight-container dimensions.

Reach for it when: Specifying or checking requirements within this document’s boundary.

ISO

Document: standard · Series; editions vary by part

Status: varies by part · as of

Authoritative for: Machine vibration evaluation.

Reach for it when: Specifying or checking requirements within this document’s boundary.

ISO

Document: standard · 2026; ed. 4

Status: current · as of

Authoritative for: Environmental management.

Reach for it when: Specifying or checking requirements within this document’s boundary.

ISO

Document: standard · 2006 + Amd1:2020

Status: current · as of

Authoritative for: Life-cycle assessment.

Reach for it when: Specifying or checking requirements within this document’s boundary.

ISO

Document: standard · 2018 + Amd1:2024

Status: current · as of

Authoritative for: Occupational health and safety.

Reach for it when: Specifying or checking requirements within this document’s boundary.

TIA

Document: standard · E (2024)

Status: current · as of

Authoritative for: Telecom bonding and grounding.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEEE

Document: standard · 2013; incorporates Cor1:2015

Status: inactive-reserved · as of

Authoritative for: Substation grounding.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEEE

Document: standard · 2005

Status: inactive-reserved · as of

Authoritative for: Equipment powering and grounding.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEEE

Document: standard · 2007

Status: inactive-reserved · as of

Authoritative for: Industrial grounding.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEEE

Document: standard · 2018 + 1547a:2020

Status: current · as of

Authoritative for: Distributed-energy interconnection.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEEE

Document: recommended practice · 2017

Status: active · as of

Authoritative for: Voltage-sag and short-interruption ride-through testing for end-use equipment below 1,000 V; the ride-through curve SPP's HILL requirement builds on (4.10).

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEEE

Document: standard · 2018

Status: current · as of

Authoritative for: Arc-flash calculations.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEEE

Document: standard · 2017

Status: current · as of

Authoritative for: Microgrid controllers.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEEE

Document: standard · 2018

Status: current · as of

Authoritative for: Microgrid-controller tests.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEEE

Document: standard · 2001

Status: inactive-reserved · as of

Authoritative for: Industrial protection.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEEE

Document: standard · 2022

Status: current · as of

Authoritative for: Transmission-connected inverter resources.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEEE

Document: standard · 2022

Status: current · as of

Authoritative for: Storage sanitization.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEEE

Document: standard · 2018

Status: current · as of

Authoritative for: Load-flow studies.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEEE

Document: standard · 2018

Status: current · as of

Authoritative for: Short-circuit studies.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEEE

Document: standard · Series; editions vary by part

Status: varies by part · as of

Authoritative for: Equipment protection.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEEE

Document: standard · 1997

Status: inactive-reserved · as of

Authoritative for: Industrial power-system analysis.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEEE

Document: standard · 2020

Status: current · as of

Authoritative for: Stationary lead-acid battery maintenance.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEEE

Document: standard · 2022

Status: current · as of

Authoritative for: Harmonic control.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEEE

Document: recommended practice · 2018

Status: active · as of

Authoritative for: Transformer capability under nonsinusoidal currents; use the offered transformer and applicable method. Catalog scope opened; paid clauses are a separate access requirement.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEEE PC57.110 ↗Access terms not published
IEEE

Document: revision project · PAR approved 2026-02-12

Status: active PAR; not a published replacement · as of

Authoritative for: Two-winding transformer scope; excludes rectifier transformers per the public project description. Catalog opened; draft clauses not accessed, access terms not established.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEEE P80 ↗Access terms not published
IEEE

Document: guideline · PAR 2025-09-10; draft ID not public

Status: draft · as of

Authoritative for: Substation grounding revision.

Reach for it when: Specifying or checking requirements within this document’s boundary.

ISO

Document: standard · Series; Part 1:2016

Status: varies by part · as of

Authoritative for: Machine vibration; select machinery part. Excludes floor/pipe-support limits.

Reach for it when: Specifying or checking requirements within this document’s boundary.

efficiency metrics

Choose the applicable document and edition before writing acceptance criteria. Publication status does not establish local adoption or product compliance.

ISO/IEC

Document: standard · 2016

Status: current · as of

Authoritative for: KPI boundaries.

Reach for it when: Specifying or checking requirements within this document’s boundary.

ISO/IEC

Document: standard · 2026

Status: current · as of

Authoritative for: PUE.

Reach for it when: Specifying or checking requirements within this document’s boundary.

ISO/IEC

Document: standard · 2016

Status: current · as of

Authoritative for: Renewable energy factor.

Reach for it when: Specifying or checking requirements within this document’s boundary.

ISO/IEC

Document: standard · 2017 + Amd 1:2025

Status: current · as of

Authoritative for: Server energy efficiency.

Reach for it when: Specifying or checking requirements within this document’s boundary.

ISO/IEC

Document: standard · 2017 + Amd 1:2025

Status: current · as of

Authoritative for: Server utilization.

Reach for it when: Specifying or checking requirements within this document’s boundary.

ISO/IEC

Document: standard · 2021

Status: current · as of

Authoritative for: Energy reuse factor.

Reach for it when: Specifying or checking requirements within this document’s boundary.

ISO/IEC

Document: standard · 2023

Status: current · as of

Authoritative for: Cooling efficiency ratio.

Reach for it when: Specifying or checking requirements within this document’s boundary.

ISO/IEC

Document: standard · 2022

Status: current · as of

Authoritative for: Carbon usage effectiveness.

Reach for it when: Specifying or checking requirements within this document’s boundary.

ISO/IEC

Document: standard · 2022

Status: current · as of

Authoritative for: Water usage effectiveness.

Reach for it when: Specifying or checking requirements within this document’s boundary.

CENELEC / BSI

Document: standard · 2016

Status: current · as of

Authoritative for: KPI boundaries.

Reach for it when: Specifying or checking requirements within this document’s boundary.

CENELEC / BSI

Document: standard · 2016 + A1:2019

Status: current · as of

Authoritative for: Renewable energy factor.

Reach for it when: Specifying or checking requirements within this document’s boundary.

CENELEC / BSI

Document: standard · 2020

Status: current · as of

Authoritative for: Energy reuse factor.

Reach for it when: Specifying or checking requirements within this document’s boundary.

CENELEC / BSI

Document: standard · 2020

Status: current · as of

Authoritative for: Cooling efficiency ratio.

Reach for it when: Specifying or checking requirements within this document’s boundary.

CENELEC / BSI

Document: standard · 2022

Status: current · as of

Authoritative for: Water usage effectiveness.

Reach for it when: Specifying or checking requirements within this document’s boundary.

hardware and fabric specifications

Choose the applicable document and edition before writing acceptance criteria. Publication status does not establish local adoption or product compliance.

OCP

Document: specification · 1.1

Status: current · as of

Authoritative for: Rack interface.

Reach for it when: Specifying or checking requirements within this document’s boundary.

OCP

Document: specification · 1.0

Status: current · as of

Authoritative for: Wide-rack interface.

Reach for it when: Specifying or checking requirements within this document’s boundary.

OCP

Document: specification · 1.0

Status: current · as of

Authoritative for: Meta wide-rack design.

Reach for it when: Specifying or checking requirements within this document’s boundary.

OCP

Document: guideline · 0.1

Status: draft · as of

Authoritative for: IT canister design.

Reach for it when: Specifying or checking requirements within this document’s boundary.

OCP

Document: specification · Revision 1

Status: current · as of

Authoritative for: Cold-plate qualification.

Reach for it when: Specifying or checking requirements within this document’s boundary.

OCP

Document: specification · Revision 2

Status: current · as of

Authoritative for: Cooling-loop qualification.

Reach for it when: Specifying or checking requirements within this document’s boundary.

OCP

Document: specification · v0.7.0

Status: current · as of

Publication record ↗

Authoritative for: Sidecar rack and power base.

Reach for it when: Specifying or checking requirements within this document’s boundary.

OCP

Document: specification · MGX rack/trays rev. 1.0

Status: current · as of

Authoritative for: NVIDIA MGX contributed rack/tray interfaces.

Reach for it when: Specifying or checking requirements within this document’s boundary.

OCP

Document: guideline · 1.2 (2025-08)

Status: current · as of

Authoritative for: Hardware security appraisal.

Reach for it when: Specifying or checking requirements within this document’s boundary.

CHIPS Alliance / OCP

Document: specification · 2.0; main spec v1.0

Status: current · as of

Authoritative for: Silicon root of trust.

Reach for it when: Specifying or checking requirements within this document’s boundary.

UEC

Document: specification · 1.0

Status: superseded · as of

Publication record ↗

Authoritative for: Ethernet transport for AI/HPC.

Reach for it when: Specifying or checking requirements within this document’s boundary.

UEC

Document: specification · 1.0.3

Status: current · as of

Publication record ↗

Authoritative for: Ethernet transport for AI/HPC.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IBTA

Document: specification · Release 2.1

Status: current · as of

Authoritative for: Transport and architecture.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IBTA

Document: specification · Release 2.1

Status: current · as of

Authoritative for: Physical links.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEEE

Document: standard · 2022

Status: current · as of

Authoritative for: Ethernet MAC and PHY.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEEE

Document: standard · 2024

Status: current · as of

Authoritative for: Ethernet high-speed PHY amendment.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEEE

Document: standard · D3.2

Status: draft · as of

Authoritative for: Next Ethernet PHY amendment.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEEE

Document: standard · 2011

Status: superseded · as of

Authoritative for: Priority flow control.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEEE

Document: standard · 2019

Status: current · as of

Authoritative for: Packet-network clock synchronization.

Reach for it when: Specifying or checking requirements within this document’s boundary.

OIF

Document: specification · OIF-800ZR-01.0 (2024)

Status: current · as of

Authoritative for: Coherent optical interoperability.

Reach for it when: Specifying or checking requirements within this document’s boundary.

UALink Consortium

Document: specification · 1.0

Status: current · as of

Publication record ↗

Authoritative for: Initial scale-up protocol.

Reach for it when: Specifying or checking requirements within this document’s boundary.

UALink Consortium

Document: specification · 2.0

Status: current · as of

Authoritative for: Common scale-up semantics.

Reach for it when: Specifying or checking requirements within this document’s boundary.

UALink Consortium

Document: specification · 2.0

Status: current · as of

Authoritative for: Data-link and physical layers.

Reach for it when: Specifying or checking requirements within this document’s boundary.

UALink Consortium

Document: specification · 1.0

Status: current · as of

Authoritative for: Data-link and physical layers.

Reach for it when: Specifying or checking requirements within this document’s boundary.

UALink Consortium

Document: specification · 1.01

Status: current · as of

Authoritative for: Chiplet integration.

Reach for it when: Specifying or checking requirements within this document’s boundary.

UALink Consortium

Document: specification · 1.0

Status: current · as of

Authoritative for: Fabric management.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEEE P802.1Qdw ↗Access terms not published
IEEE

Document: standard · PAR approved 2022-09-21; no current draft

Status: draft · as of

Authoritative for: Source flow control project; no published standard.

Reach for it when: Specifying or checking requirements within this document’s boundary.

Individual authors; IETF Datatracker

Document: specification · draft-ravi-ippm-csig-01 (2024-02-02)

Status: historical · as of

Authoritative for: Expired 2024-08-05; experimental proposal, not an RFC.

Reach for it when: Specifying or checking requirements within this document’s boundary.

OIF

Document: specification · OIF-ELSFP-02.0 (2025-01)

Status: current · as of

Authoritative for: External laser interface; does not qualify optical-engine FRUs.

Reach for it when: Specifying or checking requirements within this document’s boundary.

Ultra Ethernet Consortium

Document: specification · UE 1.0.3 transport layer (2026-07-16)

Status: current · as of

Authoritative for: Transport portion of UE specification; profile support separately qualified.

Reach for it when: Specifying or checking requirements within this document’s boundary.

TIA FOTC

Document: report · Undated; IEEE 802.3bs-2017 application

Status: current · as of

Authoritative for: Four SMF lanes per direction; eight fibers; application note.

Reach for it when: Specifying or checking requirements within this document’s boundary.

TIA FOTC

Document: report · Undated; IEEE 802.3df-2024 application

Status: current · as of

Authoritative for: Eight SMF lanes per direction; sixteen fibers; application note.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEEE

Document: standard · 2017; incorporated into IEEE 802.3-2022

Status: superseded · as of

Authoritative for: 200/400 Gb/s Ethernet amendment, including DR4.

Reach for it when: Specifying or checking requirements within this document’s boundary.

security and law

Choose the applicable document and edition before writing acceptance criteria. Publication status does not establish local adoption or product compliance.

IEC / ISA

Document: standard · 2013

Status: current · as of

Authoritative for: Control-system security requirements.

Reach for it when: Specifying or checking requirements within this document’s boundary.

ISO/IEC

Document: standard · 2022 + Amd 1:2024

Status: current · as of

Authoritative for: Information-security management.

Reach for it when: Specifying or checking requirements within this document’s boundary.

ISO/IEC

Document: standard · 2023

Status: current · as of

Authoritative for: AI management system.

Reach for it when: Specifying or checking requirements within this document’s boundary.

EU

Document: regulation · Regulation (EU) 2024/1689

Status: current · as of

Authoritative for: AI-system and GPAI obligations.

Reach for it when: Specifying or checking requirements within this document’s boundary.

EU

Document: regulation · Directive (EU) 2022/2555

Status: current · as of

Authoritative for: Cybersecurity duties for in-scope entities.

Reach for it when: Specifying or checking requirements within this document’s boundary.

EU

Document: regulation · Directive (EU) 2023/1791

Status: current · as of

Authoritative for: Energy efficiency and reporting.

Reach for it when: Specifying or checking requirements within this document’s boundary.

Germany

Document: regulation · 13 November 2023

Status: current · as of

Authoritative for: German energy-efficiency duties.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEC

Document: standard · 2024; ed. 2.0

Status: current · as of

Authoritative for: IACS asset-owner security program.

Reach for it when: Specifying or checking requirements within this document’s boundary.

IEC

Document: standard · 2020; ed. 1.0

Status: current · as of

Authoritative for: IACS system-design risk assessment, zones and conduits.

Reach for it when: Specifying or checking requirements within this document’s boundary.

Reference designs and platform documentation

Vendor material is authoritative about the vendor's own product and nothing else. The guide compares across vendors on fixed axes; when you have chosen one, its documentation governs the build.

Schneider Electric

Authoritative for: Engineered facility reference designs for AI halls (RD100, RD48 and successors) and a broad catalog of facility trade-off calculators: build vs colo, cooling architecture, economizer PUE by location, UPS economics, distribution efficiency.

Reach for it when: A bounded, engineered configuration to start from, and a calculator that matches the exact architectural fork you are weighing.

What this guide adds: Vendor-neutral comparison, the workload and economics context, and the register's dated provenance.

Complements Part 4 · Part 5 · Part 6
Vertiv

Authoritative for: Configured power, cooling and rack reference designs for named accelerator generations (GB300-class and beyond).

Reach for it when: The physical-infrastructure bill of materials for a named platform.

Complements Part 4 · Part 5
Eaton

Authoritative for: Electrical distribution, grid-interaction and modular power engineering material for high-density AI loads.

Reach for it when: Electrical product choices and the engineering behind them; separate the engineering papers from the marketing.

Complements Part 4
NVIDIA

Authoritative for: Rack, network, storage and management integration for a named generation; the executable basis for building and accepting an NVIDIA cluster.

Reach for it when: The supported topology, BOM and acceptance requirements once the platform is NVIDIA.

Complements Part 7 · Part 8 · Part 9 · Part 13
AMD

Authoritative for: Cluster design, networking with multiple fabric partners, BOMs, acceptance guidance and the facility interface for MI3xx platforms.

Reach for it when: The supported implementation once the platform is AMD; the counterpart to the SuperPOD guides.

Complements Part 7 · Part 8 · Part 13

Networking and fabrics

Part 8 is a map. These are the territory: firsthand production accounts, a peer-reviewed textbook, and the consortium specifications.

Pearson / Cisco Press (2026) — Subramaniam, Styszynski, Tambakuwala; technical reviewer credited

Authoritative for: Structured, vendor-agnostic AI networking education — scale-up and scale-out fabrics, transports, congestion control, optics, operations — with worked material and review questions.

Reach for it when: Learning AI networking properly, or checking Part 8 against a peer-reviewed treatment.

What this guide adds: The links from fabric decisions to cooling, power, procurement, commissioning and cost.

Complements Part 8
Meta

Authoritative for: A firsthand account of two 24k-GPU clusters, one RoCE and one InfiniBand, both tuned to equivalent performance on GenAI workloads — the primary evidence against any universal transport ranking.

Reach for it when: Whether Ethernet can carry your training workload, and what the tuning actually involved.

Complements Part 8 · Part 10 · Part 14

Energy, grid and flexibility

For demand forecasts, interconnection data and flexibility programs, go to the institutions that produce them. Part 3, 4 and 15 explain what they mean for a specific site.

International Energy Agency (2025 report; 2026 follow-up)

Authoritative for: Global data-center electricity demand scenarios, supply implications and methodology; the reference forecast most policy discussion cites.

Reach for it when: Demand-growth numbers you will be asked to defend; scenario ranges rather than a single trajectory.

Complements Part 3 · Part 15 · Part 16
Lawrence Berkeley National Laboratory

Authoritative for: Energy assessment tools, the US data-center energy report, and the annual Queued Up interconnection-queue dataset the guide's queue figures come from.

Reach for it when: The primary queue statistics and the methodology caveats that go with them.

Complements Part 3 · Part 15
EPRI DCFlex ↗Free + paid tiers
Electric Power Research Institute

Authoritative for: Applied research and utility demonstrations of data-center load flexibility, the utility-side view of curtailable interconnection.

Reach for it when: Turning a flexibility idea into a program a utility will recognise.

Complements Part 3 · Part 4 · Part 15
Sijbrandij Foundation

Authoritative for: A phased power co-development framework and a coalition directory for getting large loads energized faster.

Reach for it when: A structured process for the utility and generation conversations in Part 3.

Complements Part 3

Economics, benchmarks and market data

The guide's calculators are screening tools. These are the measured or modelled sources you underwrite against.

SemiAnalysis

Authoritative for: Original supply-chain (CoWoS, HBM), rack-teardown and fabric-economics research; InferenceX serving benchmarks by model, stack, precision and SLO; ClusterMAX GPU-cloud ratings. Institutional TCO models are licensed separately.

Reach for it when: Procurement or investment-grade economics, and measured serving envelopes instead of the guide's illustrative throughput constants.

What this guide adds: A common vocabulary across facilities and finance, and the register's separation of what is measured from what is modelled. About a tenth of the register's referenced claims cite SemiAnalysis — treat it as one evidentiary source, not a cross-check of itself.

Complements Part 1 · Part 7 · Part 8 · Part 16
MLCommons

Authoritative for: Governed, reproducible performance (and optional power) measurements with rules, metadata and code links.

Reach for it when: Comparing accelerators within a benchmark's bounds before believing any vendor ratio, including the ones quoted here.

Complements Part 7 · Part 10
Microsoft Research · UT Austin (2026)

Authoritative for: An analytical model that treats hardware refresh as an optimisation variable across build, refresh and inference operations.

Reach for it when: Refresh and lifecycle economics beyond the fixed-exit-multiple screen in the project-finance calculator.

Complements Part 1 · Part 14 · Part 16
JLL · CBRE

Authoritative for: Regional vacancy, pricing, pipeline and lead-time conditions by market, published on a cadence.

Reach for it when: Market-specific availability and price before a siting decision; the guide's regional pages summarise, these are the source.

Complements Part 1 · Part 2 · Part 3

Whole-system reasoning and learning

If you want to understand why the machine behaves the way it does rather than what to buy, start here.

Barroso, Hölzle, Ranganathan — Google (2018)

Authoritative for: The original warehouse-scale-computer argument: co-design, cost models, failure handling and energy proportionality, from the people who ran it.

Reach for it when: Enduring architecture and economics reasoning; the component numbers are dated, the reasoning is not.

Complements Part 0 · Part 1 · Part 12 · Part 14
Google DeepMind authors (2025, revised online)

Authoritative for: Systems mathematics of training and inference: arithmetic intensity, parallelism, rooflines, KV-cache and batching, with derivations and exercises (TPU-centred, GPUs included).

Reach for it when: Any time the guide asserts a bandwidth-bound or compute-bound regime and you want the derivation.

Complements Part 1 · Part 7 · Part 8 · Part 9 · Part 10

Following the field

The numbers here move monthly. These are the original-reporting sources the register is checked against between publishes.

Data Center Dynamics ↗Free + paid tiers
DCD

Authoritative for: Daily project, facility, power and market reporting; DCD Academy courses.

Reach for it when: What happened this week; the register lags it by design.

Complements Part 2 · Part 3 · Part 16
Data Center Richness ↗Free + paid tiers
Substack newsletter

Authoritative for: Named-analyst commentary on facilities, investment and the operators building them.

Reach for it when: Perspective on the deals and developers behind the capacity numbers.

Complements Part 1 · Part 2 · Part 16

Missing something that belongs here? Tell us through the contact form. The bibliography behind individual figures lives on the register; Appendix E maps the learning and community landscape in more depth.