OCP's DCF Power Distribution LVDC white paper v1.1.0 (2026-09-02) proposes U5 = 840 VDC as the interoperability anchor and highest designed protection voltage for 800 VDC distribution, with sources constrained not to exceed it and the band below 760 VDC (800 VDC −5%) optional.

840 VDCobserved

Value kindobserved — Reported measurements, counts, and specifications keep the precision and scope stated by their source; an exact specification is not treated as a range.
ScopeA proposal in a white paper, not a published standard or a product rating. The paper also treats ±750 VDC or 1,500 VDC as the next LVDC step; 1,500 VDC is the low-voltage DC limit.
As of2026-09
SourceOpen Compute Project, Data Center Facility – Low Voltage Direct Current Power Distribution white paper, version 1.1.0, 2 September 2026 (Power Distribution sub-project) · §5.7 Interoperable Voltage Band Proposal (PDF pp. 69–70); §5.6.1 / Figure 5.14 (U5 protection value)
Reviewchecking…review by 2027-03-17 · standard cadence
Recorded changeslast 2026-10-17
Claim idocp-lvdc-white-paper-u5-840-vdc