Appendix B
In this chapter · 4 sections
Reference Designs & Worked Examples
Choose the accelerator and counted reference population, then reconcile rack power, supporting IT, flow, fiber, ports and quoted dollars at their own boundaries; this appendix integrates two reference builds.
What you'll decide here
- Start from the per-archetype design-basis sheet, then freeze the named product: density, cooling, fabric blocking, redundancy and GPU:CPU/storage/network ratios require the workload and service tests in Chapters 1.7, 7.13 and 8.5.
- Treat the scalable unit (SU) as the atomic rack purchase and deployment block: multiply its rack population, then recount shared CDUs, fabric tiers, storage and supporting IT at the new campus or cluster size.
- Use the 50 MW campus and 100k-GPU BOM as order-of-magnitude calibrators: counts follow the stated ratios; the August 2025 server estimate, 2026 assumed allowances and unquoted networking have distinct purchase boundaries. Obtain project quotes before releasing capital.
- When a vendor proposal disagrees on racks, CDUs, switches or optics, reconcile the count before signing: oversubscription, redundancy, generation and purchase scope explain differences; no universal percentage tolerance makes a missing core acceptable.
- Re-derive, do not interpolate, when you change generation (GB200 → GB300 → Vera Rubin → Kyber): density, flow, and busbar current step discontinuously, so the multipliers in §2 are generation-stamped on purpose.
This appendix is the reusable arithmetic layer behind Part 1's archetype framework (Chapter 1.1) and Part 1's requirements matrix (Chapter 1.7). It does four things, in order: (1) a per-archetype design-basis sheet that freezes the inputs every later number inherits; (2) a scalable-unit (SU) budget giving the power, cooling, water, and network draw of one atomic deployment block per accelerator generation; (3) a 50 MW campus sized from the SU up, with the power chain, cooling plant, and water loop derived; and (4) a 100k-GPU cluster reference BOM with counts and costs for GPUs, racks, CDUs, switches, optics and storage: an August 2025 GB200 estimate, 2026 assumptions and unquoted networking.
The method throughout is multiplier-first. A reference design is a chain of ratios: GPUs per rack, racks per SU, kW per rack, L/min per kW, NICs per node, optics per NIC, GB/s per GPU of storage. Once those are pinned, rack aggregates are multiplications you can audit; shared plant and fabric tiers need the explicit ledgers below. Counts in the tables are exact arithmetic from the stated ratios. Dated server estimates and assumed allowances need project quotes before budget release. Density, flow, and current figures are generation-stamped because they step discontinuously across GB200 → GB300 → Vera Rubin → Rubin Ultra Kyber; do not interpolate across a generation boundary.
1. Per-archetype design-basis sheets
The design-basis sheet is the single page that everything downstream inherits — the concrete instantiation of the workload-profile and design-basis artifacts named in Chapter 1.1. Choose the column that matches your dominant archetype, and the rest of the appendix is parameterized for you. The two reference builds in §3–§4 use the frontier-training column unless noted, because it is the most constraining; an inference-shaped build has its own basis: enterprise HGX relaxes density and fabric, while frontier serving runs the same NVL72-class racks and often buys more service redundancy, not less.
| Parameter | Frontier training | Post-training / RL | Online inference (frontier / enterprise) | Batch inference | Edge inference |
|---|---|---|---|---|---|
| Dominant accelerator | GB200/GB300 NVL72 | Disaggregated: NVL72 trainer + HGX rollout | Frontier: GB300 NVL72; enterprise: HGX B300 / RTX PRO | HGX B200; prior-gen acceptable | L4/L40S, Jetson, single B200 |
| Named NVL72 rack quantities | HPE GB200: 132 kW nominal; Lenovo GB300: 135 kW nominal / up to 155 kW workload-dependent peak | Trainer: HPE GB200 132 kW nominal | Frontier: Lenovo GB300 135 kW nominal / up to 155 kW workload-dependent peak | Select batch product separately | Select edge product separately |
| Illustrative workload rack densities | Use the named training product above | Rollout: assumed 40–60 kW HGX | Enterprise: assumed 40–60 kW HGX | Batch: assumed 30–60 kW | Networked edge DC: assumed 5–50 kW |
| Cooling modality | DLC mandatory, warm-water | DLC trainer + RDHx/air rollout | Frontier: DLC mandatory; enterprise: air or RDHx | Air often sufficient | Air / sealed modular |
| Scale-up domain | 72 GPUs (→144, →576) | 72 trainer / 8 rollout | 72 (frontier NVL72); 8 (enterprise HGX node) | 8 | 1 (single node) |
| Scale-out fabric | Measured collectives + step-time target | Derive trainer and rollout tiers separately | Measured request/KV/EP traffic + tail SLO | Measured throughput traffic + completion target | Measured local traffic + WAN/SLO boundary |
| Fabric transport | InfiniBand XDR or Spectrum-X | IB trainer / RoCE rollout | Ethernet/RoCE common | Ethernet, cost-optimized | Standard IP |
| GPU:CPU ratio | 2:1 (NVL72: 72G:36C) | 2:1 trainer / 4–8:1 rollout | 2:1 frontier NVL72; 4:1–8:1 enterprise | 8:1+ | 1:1 appliance |
| GPU:storage (BW) | Derive loader, checkpoint drain and restore independently (9.4/9.8) | Trainer like training | KV-cache tier and prefill/decode disaggregation; model load tier | Streaming object tier | Local NVMe only |
| Resilience inputs (not topology) | Checkpoint/restart loss; maintenance/fault states; recovery SLO | Trainer/rollout state models; staleness and recovery limits | Serving SLO; replica/zone/region capacity; site-state continuity | Queue/backlog and completion limits; recovery contract | Latency routing, backhaul dependence, fleet correlation and recovery |
| Electrical design basis | Named OEM peak + facility basis — never a TDP multiplier | Per named trainer / rollout products | Frontier: named OEM facility basis; enterprise: nameplate + measured profile | Named product figures | Named product figures |
| Siting driver | Cheap firm MW + cold climate | Follows dominant sub-workload | Sub-50 ms to users | Cheapest / curtailable MW | Latency budget (30/50/100 ms) |
Scope & caveats
HPE GB200 only; printed peak and recommended busway quantity, not a continuous facility duty. Obtain OEM clarification of the inconsistent multiplier and peak duration.
2. The scalable unit (SU): power / cooling / water / network budget
The scalable unit is the atomic deployment and costing block — order it, integrate it at the factory (L11/L12), ship it, energize it, repeat. Sizing the SU once and then multiplying is what makes campus and cluster arithmetic tractable. We anchor the SU to the NVIDIA DGX SuperPOD GB200 reference: 8 × NVL72 racks = 576 GPUs per SU, with the full SuperPOD at 16 SUs (128 racks, 9,216 GPUs). The budget below gives one SU's draw across four generations; later sections count SUs, not racks.
The cross-generation columns exist because the multipliers step. A GB200 SU is ~1.06 MW of IT; the same 8-rack SU at Kyber density (~600 kW/rack) is ~4.8 MW — a 4.5× jump in what eight racks draw; qualify the Kyber rack's dimensions, mass, and service clearances before assuming it lands on the same footprint. This is the density-ramp trap from Chapter 1.1 as a budget line: the floor, water, and busbar you reserve today must survive it.
| Metric | HPE GB200 NVL72 (2026 receipt) | Lenovo NVIDIA GB300 NVL72 (2025–26) | Vera Rubin: Pegatron power / NVIDIA facility basis | Kyber NVL144 (H2 2027) |
|---|---|---|---|---|
| GPUs per SU | 576 | 576 | 576 (72/rack; 1,152 dies) | 1,152 (144/rack; 4,608 dies) |
| Rack power (TDP / Max Q) | 132 kW | 135 kW nominal TDP (Lenovo LP2357, August 30, 2026) | 188 kW Max Q | ~600 kW (facility planning point; TDP not published) |
| IT power per SU (TDP / Max Q) | ~1.06 MW | 1.08 MW | ~1.50 MW (Max Q) | ~4.8 MW (planning point) |
| IT power per SU (peak / facility basis) | HPE peak/busway: dated record above; multiplier conflict requires OEM clarification | Up to ~1.24 MW (8 × Lenovo’s up-to-155 kW peak); obtain Lenovo project electrical design requirements | ~1.82 MW Max P / ~2.64 MW facility basis (330 kW/cabinet) | not published; size to the ~600 kW/rack planning point |
| DLC heat to liquid | ~0.92 MW | ~0.97 MW (assumed 90%) | ~1.50 MW (assumed 100% liquid, Max Q) | ~4.8 MW (assumed 100% liquid) |
| Residual air heat | ~0.14 MW (~17 kW/rack) | ~0.11 MW (assumed 10%) | ~0 (assumed 100% liquid) | ~0 (assumed 100% liquid) |
| Secondary-loop flow (stated water properties, 10.0 K rise) | ~1,320 L/min | ~1,400 L/min | ~2,160 L/min | ~6,900 L/min |
| Coolant inlet / ΔT target | FWS target W45; HPE publishes no technology-loop inlet maximum for this rack / 7–10 °C design rise; the 10.0 K used below is its upper end | Lenovo LP2357: up to 45 °C inlet; 10 K here is an assumed heat-balance rise | Assumed ~45 °C FWS target; qualify Pegatron TCS | Assumed ~45 °C FWS target; qualify future TCS |
| Illustrative back-end NIC ports (one 400G attachment/GPU) | 576 assumed ports | Acquire purchased port profile | Acquire purchased port profile | Acquire purchased port profile |
| Illustrative leaf host-facing ports | 576 assumed ports | Follow purchased port profile | Follow purchased port profile | Follow purchased port profile |
| Illustrative host-channel modules only | 1,152 ends; inter-switch ends counted below | Select modules from purchased port profile | Select modules from purchased port profile | Select modules from purchased port profile |
| Storage service per SU | Acquire loader and checkpoint budgets (9.4/9.8) | Acquire workload-specific budgets | Acquire workload-specific budgets | Acquire workload-specific budgets |
Scalable-unit inputs for the two reference builds
Take the GB200 column and walk it forward so the multipliers are explicit. GPUs: 8 racks × 72 GPUs = 576. IT power (TDP): 8 × 132 kW = 1.056 MW ≈ 1.06 MW. Electrical chain: use HPE’s facility guidance and Chapter 4.5’s transient budget, not a TDP multiplier. Heat split: at ~115 kW liquid + ~17 kW air per rack, liquid carries 8 × 115 = 920 kW and air carries 8 × 17 ≈ 140 kW (unrounded nominal sum: 920 + 136 = 1,056 kW). Flow illustration: keep the 920 kW liquid heat boundary fixed. With the stated water properties and 10.0 K rise, 920 kW × 60,000 / (998 × 4.182 × 10.0) ≈ 1,320 L/min for the SU (about 165 L/min per rack). Recalculate with the approved fluid, operating temperature and selected ΔT; do not use the 1,056 kW total rack TDP as TCS heat. Network inputs: use Chapter 8.5’s generic one-port-per-GPU 400G ledger for the two maps below. They are illustrative, not HPE/NVIDIA qualification; inter-switch optics do not scale by a fixed per-GPU multiplier. → SU definition in Chapter 1.7; fabric sizing in Chapter 8.5.
3. Worked example: a 50 MW campus sized from the SU up
Now multiply. The brief: a 50 MW-class IT frontier-training reference campus on HPE GB200 NVL72, built as integer SUs, with the power chain, cooling plant, and water loop derived. We size the IT budget on rack TDP and the electrical chain on each platform's published peak and OEM facility design basis (HPE’s printed GB200 peak conflicts with its stated multiplier; obtain the corrected duty and duration schedule), and we reserve floor/water/busbar headroom for a GB300 → Vera Rubin density step (the irreversible substrate from Chapter 1.1).
SU count. Choose 48 SUs as a clean reference arrangement: three 16-SU SuperPOD-scale halls, or six 8-SU halls. That is 48 × 8 = 384 NVL72 racks and 48 × 576 = 27,648 GPUs. Treating 132 kW/rack as an exact nominal cap fixture, total IT is 50.688 MW of GPU-rack IT, which exceeds a hard 50.000 MW cap by 0.688 MW. If 50.000 MW is a hard cap, use at most 47 SUs: 376 racks, 27,072 GPUs, and 49.632 MW of GPU-rack IT. Supporting network, storage and management IT still have to fit: Chapter 4.1 closes the total-load ledger; Chapter 5.1 carries every residual-air and liquid duty into the plant. Neither rack count proves total-IT admission.
| Subsystem | Sizing basis | Quantity / value |
|---|---|---|
| Scalable units | Reference arrangement | 48 SUs |
| NVL72 racks | 48 × 8 | 384 racks |
| GPUs | 384 × 72 | 27,648 GPUs |
| GPU-rack IT power (nominal TDP) | 384 × 132 kW | 50.688 MW (48-SU reference) |
| Facility power (assumed PUE ≈ 1.2) | 50.688 MW × 1.2 | ~61 MW |
| Utility interconnect (N, assumed 15% margin) | 50.688 MW × 1.2 × 1.15 (round only the result) | ~70 MW POI / 2× 132 kV feeders |
| Main transformers | ≥2 × 75 MVA (N+1 at MV) | 2–3 × 75 MVA |
| MV distribution | 33/13.8 kV ring or radial | per-hall 13.8 kV → 415 V / 800 VDC |
| Ride-through stack (protected-IT boundary) | 50.688 MW continuous nominal IT; any declared rack peak/transient is allocated across rack capacitance/BBU and upstream UPS/BESS | Do not treat a sub-second rack peak multiplier as central-UPS continuous MW |
| Backup generation (generator-terminal critical-load boundary) | 50.688 MW IT × 1.2 PUE ≈ 61 MW steady, plus explicit derating/operating reserve and auxiliaries outside that boundary | ~65–75 MW is a screening installed-capacity band only if the load schedule proves it; ride-through bridges rack-side sub-second transients |
| DLC heat to facility water | 384 × 115 kW | ~44.2 MW thermal |
| CDUs (HPE 1.3 MW; maximum eight racks/CDU; local 3+1 per 24-rack pod) | 16 pods × (3 duty + 1 valved standby); each duty CDU = 8 × 115 kW = 0.920 MW | 64 installed (48 duty + 16 standby) |
| Secondary-loop flow | 44,160 kW × 60,000 / (998 × 4.182 × 10.0) | ~63,500 L/min aggregate (~165 L/min/rack) |
| Heat rejection | ~61 MW total heat | towers/dry-coolers + adiabatic, economized |
| Water make-up (assumed WUE ~0.5 L/kWh of IT energy) | 50.688 MW × 1,000 kW/MW × 0.5 L/kWh × 8,760 h/year | ~200 ML/year (about 600 m³/day average; size permit/storage on peak-day draw) |
| Back-end fabric (400G; healthy 1:1 leaf tier) | 8 rails; 4 × 27-leaf pods/rail; 32 spines/pod | 864 leaves + 1,024 spines + 512 cores = 2,400 switches; 176,128 module ends |
| Floor area (white space) | 384 racks × assumed 30 m²/rack including aisles/CDUs | ~12,000 m² + plant (two-significant-figure layout allowance) |
| Floor loading basis | declared equivalent-uniform screen plus OEM foot/wheel, rolling and rigging reactions | verify project load combinations against the complete slab/access-floor assembly and move route |
Campus port map. In each rail/pod, leaf ports 1–32 face hosts and 33–64 face spines 1–32. Each spine uses 1–27 for leaves, 28–32 dark, 33–48/49–64 for its two group cores. Each core’s four consecutive 16-port groups face the four pods’ matching spine. Every cable end has one address. The ledger totals 27,648 host + 27,648 leaf–spine + 32,768 spine–core = 88,064 channels, 176,128 module ends and 704,512 active fiber paths; surveyed lengths determine fiber-kilometers, and electrical lanes are separate.
At 108 leaves/rail the campus exceeds Chapter 8.5’s 64-leaf two-tier limit. Include the core; at ≤16,384 GPUs its two-tier instance becomes eligible. Release only after Chapter 13.7/Chapter 13.9 pass the purchased stack and failure states. A spare chassis repairs an outage; it cannot keep a single-attached rank connected.
4. Reference BOM: a 100k-GPU GB200 cluster
The flagship build: a 100,000-GPU GB200 reference training cluster, costed as a bill of materials. Built from the SU: ceil(100,000 ÷ 576) = 174 SUs minimum; choose eleven 16-SU halls, hence 176 SUs = 1,408 NVL72 racks = 101,376 GPUs (≈ 100k). At 132 kW/rack that is ~186 MW GPU-rack IT and ~220 MW facility for that fixture at assumed PUE 1.2. Add separately counted supporting IT before a project capacity release. That capacity may be delivered on one qualified campus or split across sites; DCI does not imply that this illustrative logical cluster runs as one cross-site synchronous job (Chapter 8.8).
The figures use SemiAnalysis’s August 2025 server-only estimate and explicitly assumed storage/CDU/plant costs. Use the counts as arithmetic — they balance ports, power, and flow; they do not draw a topology — and the dollars as an order-of-magnitude frame. The GPU/rack line is a major cost; its share requires priced networking and reconciled facility scope. A percentage allowance cannot supply the core.
| BOM line | Count | Basis | Unit-cost basis | Line cost (rough) |
|---|---|---|---|---|
| GB200 GPUs (rack population) | 101,376 | 176 SU × 576 | Included in the integrated rack line | Do not add a bundled network allowance to the counted fabric |
| NVL72 racks (integrated, L11) | 1,408 | 176 × 8 | Server estimate below | Subtotal below |
| — includes GPUs, Grace, NVSwitch and DLC | — | 101,376 × unrounded per-GPU server cost = same subtotal | Equivalent server scope | Included above |
| CDUs (HPE 1.3 MW; maximum eight racks/CDU; local 3+1 pods) | 235 installed | 1,408 racks: 176 duty; 58 full 24-rack 3+1 pods plus one final 16-rack 2+1 pod | Illustrative unit allowance below | 235 × allowance; rounded subtotal below |
| Back-end leaves (64×400G) | 3,168 | 8 rails × 396 leaves; 32 host + 32 uplink ports | Acquire switch quote | 3,168 × quote |
| Back-end spines and cores | 3,328 + 2,048 | Per rail: 13 × 32 spines; 32 × 8 cores; 4 links/spine/core | Acquire both quotes | Price both tiers and module power |
| Front-end/storage; separate OOB | Acquire port schedules | 9.3 service/recovery; 8.7 management inventory | Acquire quotes | Separate fabric scope |
| Back-end modules (assumed 400G DR4) | 618,496 ends | 101,376 host + 101,376 leaf–spine + 106,496 spine–core channels; two ends/channel | Acquire module/channel quotes | 309,248 channels plus spares |
| DAC/AEC copper (intra-rack scale-up) | in-rack | 5,184 NVLink cables/rack (copper, in rack price) | incl. in rack | — |
| Hot storage (parallel FS) | ~200 PB usable | 99 × 2 PB = 198 PB usable capacity; bandwidth HOLD for workload budgets | Assumed usable-GB price below | 198M GB × price; subtotal below |
| Capacity / object tier | ~150–250 PB | Data lake + checkpoints; independent endpoints | Assumed usable-GB price below | 150M × low price to 250M × high price |
| Facility power chain | ~220 MW facility | Transformers, UPS/BESS, switchgear, generators | Assumed facility-MW price below | Unrounded MW × price; excludes shell |
| Cooling plant + water loop | ~186 MW IT | Rejection/piping/plant; excludes 235 CDUs | Assumed IT-MW price below | Unrounded MW × price; excludes shell |
| Cluster total | HOLD for complete scope | Reconcile server/facility scopes; include every fabric tier, passive plant, power and spares | Acquire quotes | An unpriced core cannot fund a build |
Large-cluster port map. Leaves keep the campus assignment. In each rail, twelve pods use spine ports 1–32 for leaves; the final pod uses 1–12, with 13–32 dark. Spine ports 33–64 face eight group cores, four ports/core. Each core’s thirteen four-port pod groups occupy 1–52; 53–64 stay dark. This maps 101,376 endpoints to 8,544 switches; all channel/module populations are in the BOM. It is a realizable map, not a minimum-switch proof.
A campus core loss removes half its group’s upper capacity; a cluster core loss removes one eighth. A leaf loss disconnects 32 ranks. Test these cuts under Chapter 8.5 with actual placement and payload service; healthy port balance does not accept a failure. Budget release stays HOLD for route, recovery, power and quote evidence. At ≤16,384 GPUs, qualifying the two-tier map can remove the core purchase.
Scope & caveats
One named Lenovo product record. These are distinct operating quantities, not a single scalar or a project electrical design rating.
Qualify the purchased configuration and transient envelope. The separate NVIDIA reference architecture figure of 142 kW is not a Lenovo design provision.
Scope & caveats
NVIDIA's published figure (GTC 2025) is 600 kW per Rubin Ultra Kyber rack and GTC 2026 did not revise it. SemiAnalysis (2026-05-26) reports Kyber Ultra 'approaching 660 kW' — a single-source analyst estimate for a 2027 part, recorded here rather than adopted, since the vendor primary figure still stands.
Scope & caveats
A guide physics result, not an OCP or OEM flow specification. Apply it only to liquid-captured heat and recalculate with the approved fluid properties, selected ΔT, pressure budget, and product operating envelope.
Scope & caveats
One named 8-rail training reference design, not a workload-name mandate. Validate the port rate, rail count, and blocking ratio against the target traffic matrix, topology, placement, failure headroom, and step-time objective.
Scope & caveats
Hyperscaler server only; rack and per-GPU costs equivalent. Network/storage/facility extra.
Scope & caveats
Assumed GB300 complete system; network/facility separate.
Scope & caveats
Server only; add separately quoted network, storage and facility.
Scope & caveats
Guide allowance; count CDUs once (Chapter 5.6).
Scope & caveats
Guide allowance, decimal usable GB (Chapters 9.6/9.8).
Scope & caveats
Guide allowance; unrounded high endpoint $12.5M, not a $10M cap (Chapter 9.6).
Scope & caveats
Guide allowance; exclude shell and cooling (Chapter 4.1).
Scope & caveats
Guide allowance; exclude the 235 CDUs and shell (Chapter 5.8).
Sensitivity: how the two builds move when you change one input
Generation step (GB200 → Vera Rubin). A future 8-rack SU must be recalculated from that named product's liquid-captured heat, approved-fluid properties and selected ΔT; the current GB200 illustration does not supply a portable flow endpoint for Vera Rubin. A hard 50 MW operating envelope at Vera Rubin density fits 33 full SUs at 188 kW Max Q (1.504 MW/SU) or 27 at 228 kW Max P (1.824 MW/SU); a 50 MW facility-basis envelope fits 18 at the 330 kW cabinet basis (2.64 MW/SU). At the 188 kW Max-Q point, nominal heat per rack is about 1.4× the 132 kW GB200 TDP fixture; the 228 kW Max-P and 330 kW facility bases are separate comparisons. Select the generation only after cooling, electrical capacity and the floor/move route pass together. Oversubscription scenario (1:1 → 2:1). Recount the 1:1 → 2:1 equipment change under 8.5, then test surviving cuts in 13.7 and workload deadlines in 13.9. Accept savings only after placement and failure states pass; another topology’s percentage cannot price this core. Dry, non-evaporative heat rejection. Moves the campus’s illustrative ~200 ML/year evaporative make-up toward zero, with loop fill and maintenance still required. At the assumed +0.05 PUE sensitivity, 50.688 MW × 0.05 adds about 3 MW of facility load; the named weather/plant curve decides that increment and the larger rejection footprint. Reject dry cooling if that load exceeds the POI or lifecycle-cost budget; Chapter 15.4 owns the WUE/PUE trade. Effective GPU life (3 yr → 5 yr). At constant installed population and utilization, 5/3 increases lifetime GPU-hours by about 67%. Annual straight-line depreciation falls to 3/5 of its former value; recurring energy and operating cost do not fall by that factor. No equipment count or initial capex changes. Use Chapter 1.8 and Appendix C to test whether the hardware remains economically useful for those extra years.
Choose the reference population whose counted fabric and surviving workload fit the project; procure the complete scope. 8.5 changes topology; 1.8 values it. An incomplete fabric allowance leaves required hardware, power and commissioning outside the purchase. Close the supporting-IT inventory with 7.13 and the counted fabric in 8.5; then 4.1 owns electrical demand and surviving source capacity, while 5.11 owns cooling flow and heat rejection with a train unavailable. The integrated release needs the actual storage, management and network load, qualified failure state and non-overlapping quotes; rack nominal MW alone releases none of those interfaces.
Cite this chapter
Fehn, J. (2026). Reference Designs & Worked Examples (Chapter B). The Definitive Guide to AI Data Centers. https://aidatacenterguide.com/appendix-appendices-and-reference-data/b-reference-designs-and-worked-examples (accessed 2026-09-29).
@misc{aidc-B,
author = {Fehn, Jacob},
title = {Reference Designs & Worked Examples (Chapter B)},
howpublished = {The Definitive Guide to AI Data Centers},
year = {2026},
url = {https://aidatacenterguide.com/appendix-appendices-and-reference-data/b-reference-designs-and-worked-examples},
note = {Accessed 2026-09-29}
}