Chapter 5.8
In this chapter · 7 sections
Heat Rejection: Chillers, Dry Coolers, Towers, Adiabatic & Economizers
Heat rejection cashes out your loop temperature against the climate, and the choice among chiller, dry cooler, wet tower, and adiabatic hybrid trades kilowatt-hours against liters every hour it runs.
What you'll decide here
- Where on the chiller → adiabatic → dry-cooler → wet-tower spectrum your plant sits — which is set first by your facility-loop supply temperature and second by the bin-hour profile of your site's climate, not by a vendor catalog.
- The water-vs-energy operating point: how many liters per kWh you are willing to evaporate to claw back PUE, given source availability, water cost, drought restrictions and the discharge permit — and whether ZLD becomes the price of siting when permitted blowdown treatment, reuse and disposal offer no better route.
- The hybrid-plant mode-sequencing logic — free-cooling / adiabatic-assist / mechanical — and the changeover wet-bulb setpoints that decide how many hours a year a compressor ever runs.
- The cooling-tower water-management program under ASHRAE 188: biocide regime, Legionella sampling, blowdown/cycles-of-concentration, and who owns it — because a skipped plan is a permit and a public-health liability, not just an O&M line.
- Plant redundancy and concurrent maintainability — and the stored water, dual-feed pumps and fast-start sequence that stand between a utility blip and a throttled cluster when the participating thermal inventory and OEM-approved response cannot bridge the gap unaided.
Everything upstream of this chapter — the cold plate, the CDU, the secondary loop, the facility water loop — moves heat from the die to a pipe of warm water on the roof or in the yard. Heat rejection is the last meter: the act of dumping that heat into the atmosphere so the loop can come back cold enough to do it again. It is the least glamorous subsystem in the building and the one that most directly sets your annualized PUE, your annual water bill, and whether the local utility and the local watershed will tolerate you. The physics is a single sentence — you can reject heat to dry air, to evaporating water, or to a refrigeration cycle that pumps it uphill — but the consequences of which one you lean on, and for how many hours a year, compound into the largest controllable line in operating cost.
One variable dominates, and you set it two chapters ago: the temperature of the water you push to the rack. Warm-water DLC (W32–W45 in ASHRAE's classes) is what makes the cheap rejection paths reachable at all; a lower supply temperature reduces the hours they can cover. So this chapter reads as a cascade from loop temperature → rejection technology → climate-bin economics → the water/energy operating point → the redundancy and ride-through the plant must carry, with a downstream cost attached to each fork. → loop temperature and the W-classes are set in Chapter 5.7; the metrics we score against are canonical in Chapter 15.1.
The rejection spectrum, ordered by what it spends
There are four families of heat-rejection plant, and the honest way to order them is by the resource each one spends to move a watt of heat into the sky. From evaporating water to spending compressor energy, compare what each path consumes at the same supply temperature, heat duty and design state:
Open cooling towers (evaporative). The thermodynamic champion: they reject heat by evaporating a fraction of the circulating water, so their floor is the ambient wet-bulb temperature, which is site- and hour-specific; calculate coincident design bins rather than applying a universal hot-afternoon depression. That low approach is why a tower-cooled plant can hold a low PUE in climates where a dry cooler would have surrendered to a compressor. The price is liters: evaporation is why its site WUE is higher than a dry system's near-zero process-water floor, plus blowdown, drift, biocide, and an ASHRAE-188 program. Open towers also expose the facility loop to airborne fouling, which is why they almost always sit behind a plate heat exchanger.
Adiabatic / evaporatively-assisted dry coolers. The hybrid middle and the fastest-growing class in 2026. A dry cooler (a finned air-to-water coil with fans) runs bone-dry most of the year; on the handful of hot, high-dry-bulb hours it cannot meet alone, a pre-cooling stage wets pads or sprays a mist into the inlet air to pull the entering air down toward its wet-bulb, recovering capacity without committing to year-round evaporation. You spend water only on the bins where the dry stage cannot close duty and assist is selected; a cool-site schedule can make those rare, while a hotter one buys many more wet hours — and trade it directly for not buying or running a chiller. This is the canonical water-vs-energy compromise instrument.
Dry coolers (sensible only). Zero process water by construction — they reject heat to dry air across a coil, like a giant car radiator. Their floor is the ambient dry-bulb, so their fortunes are entirely a function of how warm your loop is and how cool your air gets. A W40+ loop in a temperate or cold climate can run dry-cooler-only for most or all of the year, hitting a near-zero WUE and a low PUE simultaneously — the best-case outcome. The same dry cooler on an 18 °C chilled-water loop in Phoenix is a fan that cannot keep up, and a chiller has to carry the day.
Mechanical chillers (vapor-compression). The brute-force backstop: a refrigeration cycle that can deliver loop water colder than the ambient wet-bulb, at the cost of a compressor whose electrical draw is the single largest non-IT load in a chiller-based plant. Chillers exist to cover the bins the free-cooling and adiabatic paths cannot, and to serve any loop too cold for them. Every hour a compressor runs is a direct, measurable hit to PUE. In a 2026 warm-water DLC facility, the design goal is to make the chiller a rarely-used insurance policy — or to delete it entirely.
| Plant | Rejection floor | Water (WUE) | Energy (cooling PUE adder) | Best-fit loop / climate | Headline liability |
|---|---|---|---|---|---|
| Open cooling tower (evaporative) | Ambient wet-bulb | Water balance: evaporation, drift and blowdown | Pumps and tower fans; add refrigeration where required | Required supply above wet-bulb plus approach, or paired with refrigeration | Water consumption, blowdown discharge, Legionella (ASHRAE 188) |
| Adiabatic / evap-assisted dry cooler | Dry-bulb most hours; toward wet-bulb on peak bins | Makeup in selected assist bins | Low–moderate: fans; water only when assisting | Warm-water DLC (W32–W45); temperate-to-warm climates | Pad/spray hygiene, water-treatment on the assist stage |
| Dry cooler (sensible only) | Ambient dry-bulb (+ a few °C approach) | No evaporative process-water input | Moderate: large fan-power on hot days | Warm loop (W40+) in temperate/cold climates | Capacity collapses on hot-dry days; bigger footprint |
| Mechanical chiller (vapor-compression) | Below wet-bulb (sets its own setpoint) | ~0 if air-cooled condenser; high if tower-condensed | Compressor and auxiliaries at the selected duty | Any loop, incl. low-temp; hot climates as backstop | Energy cost and PUE; refrigerant GWP / F-gas rules |
Free cooling and economizers: counting bin-hours, not nameplates
"Free cooling" is a misleading name — the fans and pumps still draw power — but the term of art means rejecting heat without running a compressor. There are two economizer families, and the choice between them is mostly settled by the fact that you are cooling liquid, not air.
Air-side economization ducts filtered outside air directly to the IT, or uses an air-to-air wheel. It is the workhorse of legacy air-cooled hyperscale halls and can deliver near-1.1 PUE in cool climates — but it scales with airflow, not with a liquid loop, and it imports humidity, particulates, and (in some regions) corrosive gases that the IT must tolerate. For a dense liquid-cooled AI hall with L2L CDUs, air-side economization cools the residual room-air duty, not the heat the cold plates hand to facility water. An L2A exchanger moves its cold-plate heat into that room-air path, so count the actual rack split and heat sink. Water-side economization is the relevant lever for liquid plants: when the ambient wet-bulb (tower) or dry-bulb (dry cooler) is low enough, a plate heat exchanger lets the rejection loop cool the facility loop directly and the chiller idles. Water-side economizing is what turns a chiller plant into a part-time chiller plant.
The engineering that matters is not the nameplate — it is the bin-hour count. Take your site's TMY (typical meteorological year) wet-bulb and dry-bulb distribution, lay your loop's approach temperature over it, and read off how many of the 8,760 hours each mode covers. A warm-water loop pushes the crossover so far that, in temperate and cold climates, the compressor-hours fall to a rounding error; water-side economizing on cooling towers below the wet-bulb threshold can cut annual cooling energy by roughly 40–65% in temperate climates versus mechanical chilling alone (Alfa Laval; ScienceDirect free-cooling studies, 2023–2025). The same overlay in a hot-humid site shows the compressor carrying real load — and tells you, quantitatively, what you are buying when you site there.
Hybrid-plant mode sequencing: where the compressor-hours are actually spent
A modern AI heat-rejection plant is rarely one machine. It is a hybrid that runs three modes against changeover setpoints, and the controls logic that sequences them is where annualized PUE and WUE are actually won or lost — far more than the equipment selection. The canonical sequence, coldest ambient to hottest:
- Free-cooling (dry) mode. When the selected dry cooler's rated performance at the actual load, flow, ambient and fouling state still delivers the loop supply setpoint — not merely when ambient sits below the return temperature — modulate dry-cooler fans only. Ambient below return buys partial economization; full dry mode is a capacity result you have to select for. Zero process water, lowest energy. A warm loop keeps the plant here for the bulk of the year in most of the populated temperate world.
- Adiabatic-assist mode. As dry-bulb rises and the dry coil starts to lose its approach, stage on pre-cooling — wet the pads or pulse the spray — to drag entering-air temperature toward the wet-bulb and recover capacity. You begin spending water, but only on these bins, and you have still not started a compressor.
- Mechanical (chiller / compressor) mode. Only when even the adiabatic-assisted approach cannot hold the loop setpoint do you commit the compressor. In a well-sequenced warm-water plant in a temperate climate, this can be a few hundred hours a year or fewer; in some Nordic and high-altitude siting, effectively never.
The decision embedded in the sequence is the changeover wet-bulb (and dry-bulb) setpoints and the hysteresis band around them. Set them too aggressive — chasing the last fraction of free cooling — and the plant hunts: fans and water and compressors cycle on the boundary, churning energy and water and stressing equipment. Set them too conservative and you start the compressor on hours the adiabatic stage could have covered, paying PUE you did not owe. This is a control-tuning problem, and it is the thermal sibling of the setpoint-stability problem a later chapter (5.12) treats for the loop side. → control-loop tuning, anti-hunting, and the no-inertia transient in Chapter 5.12.
Deep dive: the bin-hour overlay that decides whether you ever buy a chiller
The most consequential heat-rejection decision — chiller or no chiller — should be made on a spreadsheet, from the site's bin-hour data. The method is a bin-hour overlay, and it is worth doing by hand once to internalize what drives it.
Start with the site's TMY data: the 8,760 hourly wet-bulb and dry-bulb temperatures, binned (say, in 1 °C buckets). Now fix your required loop supply temperature and heat duty — for a W40 DLC loop, the facility water comes back around 40–45 °C and must be cooled to, say, 35 °C supply. A dry cooler needs an approach of a few °C, so it can serve that loop whenever dry-bulb is below roughly 30 °C; an adiabatic stage extends that toward the wet-bulb on the hotter bins. Count the hours below the dry-cooler threshold (free-cooling hours), the hours between dry-cooler and adiabatic thresholds (assist hours, where you spend water), and the residual hours above (compressor hours). The compressor-hour count, multiplied by the compressor's kW, is the entire reason a chiller exists in your PUE.
Two levers move this overlay more than anything else. Raise the loop temperature and every threshold shifts up the dry-bulb axis, converting compressor-hours into free-cooling-hours wholesale — this is why W45 is so prized. Move north (or up) and the bin distribution itself shifts cold, doing the same thing. Run against a Nordic or high-desert-night weather file with a named cooler selection and load profile, a W45 loop can model zero compressor-hours — that modeled result is the first step toward deleting the chiller and banking its capex and standby losses; design-extreme, failure-state and transition capacity must close before the box can leave the BOM. Run the same loop against a tropical file and the compressor-hour count is what tells you whether you can. Neither answer travels: the count belongs to one weather file, setpoint, load profile and cooler schedule, and a TMY sizes annual energy, not the design extreme or the failure case you still have to cover. The overlay is how you turn "it depends on climate" into a number you can underwrite. → siting and the energy-water nexus screen in Chapter 3.1.
Does assist earn its water use?
Cold-bin dry supply screen = 15 + 5 = 20 °C: modulate to 30 °C. Middle-bin dry gives 33 °C, while assist gives 28 − 0.750(28 − 20) + 5 = 27 °C: use assist or mechanical cooling. Hot-bin assist gives 35 − 0.750(35 − 27) + 5 = 34 °C: mechanical cooling is required. A temperature screen does not supply a missing capacity curve.
Hybrid liquid-plant energy = 6,000 × 20.0 + 2,000 × 25.0 + 760 × 100 = 246 MWh; dry/mechanical = 6,000 × 20.0 + 2,760 × 100 = 396 MWh. IT energy is 3,504 MWh. Common overhead is (16.0 + 20.0) × 8,760 = 315.36 MWh. Facility totals round to 4.07 and 4.22 GWh; PUE is 1.16 and 1.20. Hybrid input water = 2,000 × 0.500 = 1,000 m³, giving 0.285 L/kWh IT on the declared total-input boundary. Input is not all evaporation when discharge exists.
Assist saves 150 MWh for 1,000 m³: 150 kWh avoided per m³. Choose assist when water is permitted and its marginal burden is below the value of that electrical saving. Above that crossover, or with no water allocation, choose the dry/mechanical alternative if it meets capacity. No tariff assumption is needed to expose the trade.
Both fail the stated outage: 323 − 300 = 23 kW uncovered. Add surviving duty or demonstrate an accepted reduction of at least 23 kW while retaining the air path. Annual efficiency does not release the fault state. ASHRAE heat-rejection guidance supports the method; 15.1 owns metrics, 15.4 water accounting and 13.5 installed acceptance.
The water-vs-energy frontier
Strip away the equipment and heat rejection is a single trade: liters of water against kilowatt-hours of energy. Evaporative rejection accesses the ambient wet-bulb floor, your compressor runs less, and your PUE improves — at the cost of WUE. Choose dry rejection, and cooling process-water input approaches zero while your PUE rises and (in hot climates) a compressor draws the difference. There is no costless option on this frontier; there is only the operating point that minimizes your blended cost of water and power under your permit constraints.
The numbers anchoring the frontier are stark. LBNL's 2024 U.S. fleet model projects average site WUE of 0.45–0.48 L/kWh after 2023 across the whole fleet, all cooling types — the evaporative-dominated large-facility survey average sits at ~1.8–1.9 L/kWh; designs with dry, non-evaporative heat rejection approach zero site process water. Microsoft’s FY2025 cooling-and-humidification WUE was ~0.27 L/kWh for its fully owned and controlled datacenters operating for that entire fiscal year. Its separate December 9, 2024 design announcement estimated avoiding more than 125 million liters per datacenter annually by eliminating cooling evaporation, with Phoenix and Mt. Pleasant pilots scheduled for 2026 and first new-site operation in late 2027. That design can reduce a basin’s water exposure, but its annual electrical penalty still depends on the local weather and plant curves. The fork is genuine and it is regional: in a water-rich, power-expensive Nordic site, you may evaporate freely; in an arid, power-cheap Southwest US or Gulf site, the social license and the discharge permit push you toward dry rejection even though the climate punishes it.
| Siting context | Rational rejection choice | WUE outcome | PUE outcome | Binding constraint |
|---|---|---|---|---|
| Cold + water-rich (Nordic, PNW) | Test dry/economizer duty against actual extremes and unavailable units | Calculate makeup and discharge in the selected modes | Sum annual equipment input on the same IT-energy boundary | Almost none — the easy case |
| Temperate + balanced | Adiabatic hybrid; water on peak bins only | Calculate makeup and discharge in the selected modes | Sum annual equipment input on the same IT-energy boundary | Tuning the changeover setpoints |
| Hot-arid + water-scarce | Dry cooler + chiller backstop; minimize/avoid evaporation | Calculate makeup and discharge in the selected modes | Sum annual equipment input on the same IT-energy boundary | Water permit / drought; ZLD if any blowdown |
| Hot-humid (tropical) | Evaporative tower (wet-bulb still helps) or chiller | Calculate makeup and discharge in the selected modes | Sum annual equipment input on the same IT-energy boundary | No good free-cooling window; both options carry cost |
Cooling-tower water management: ASHRAE 188, Legionella, blowdown, ZLD
Choose the obligation by evaporative design, not the marketing label. Open towers and evaporative condensers require water treatment and Legionella risk management; recirculating spray adiabatic systems require a design-specific risk assessment, while once-through wetted media without stored or recirculated water or aerosol follows a lower-risk control path. A cooling tower is, by aerosol physics, the single highest-risk water system in an industrial facility for Legionella pneumophila: it warms water to the bacterium's growth range and then sprays it into the air. ANSI/ASHRAE Standard 188 (current edition 2021) is the consensus standard that governs the response — its applicable building-water-system requirements call for a Water Management Program; statutory adoption is jurisdiction-specific: a documented analysis of the water system, defined control limits at critical control points (disinfectant residual, temperature), monitoring, corrective actions, and verification records. In the US this is reinforced by CDC guidance. Skipping it is not an O&M shortcut — it is a liability and, in several jurisdictions, an operating-permit violation.
The operational mechanics that the program governs:
- Biocide regime. Oxidizing (chlorine/bromine) and non-oxidizing biocides on a dosing schedule, plus dispersants to break biofilm — the substrate Legionella actually hides in. The treatment chemistry interacts with corrosion and scale control, so it is a coupled water-chemistry problem, not three independent ones.
- Cycles of concentration and blowdown. As water evaporates, dissolved solids concentrate; "cycles of concentration" is how many times you let them concentrate before bleeding off (blowdown) and replacing with fresh makeup. More cycles save makeup water but raise scaling and corrosion risk and concentrate the blowdown stream you must discharge. This single ratio sets both your makeup-water draw and your discharge volume.
- Drift. Droplets carried out of the tower by the airflow — minimized by drift eliminators both to cut water loss and to limit aerosol dispersal of any contamination.
The discharge side is where arid siting collides with environmental permitting. Tower blowdown is a concentrated brine; a facility cannot always send it to a municipal sewer (volume, salinity, biocide residuals), and in a closed-basin arid region there may be no surface water to discharge to at all. Zero-liquid-discharge (ZLD) can rescue an otherwise blocked evaporative design when the site has no acceptable permitted liquid-disposal route: an on-site treatment train — typically reverse osmosis followed by thermal evaporation/crystallization — that recovers most of the water for reuse and reduces the waste to a solid salt cake for landfill, discharging essentially no liquid. ZLD is energy- and capex-intensive and is rarely chosen for its own sake; it is chosen because it is the price of admission to evaporative cooling in a basin that will not issue a discharge permit otherwise. Framed as a decision: in an arid, discharge-restricted site, your options include dry rejection (no cooling-tower blowdown) or evaporative rejection with permitted treatment, reuse and disposal; where liquid disposal is unavailable, ZLD recovers blowdown on site and adds its own energy and capital bill — and the ZLD capex/energy is the toll for keeping the wet-bulb advantage. → discharge and withdrawal permitting as a siting critical-path item in Chapter 3.9; the water screen in siting in Chapter 3.1.
Scope & caveats
The near-zero endpoint requires dry, non-evaporative heat rejection; loop closure alone does not determine WUE-site.
Scope & caveats
Fully owned and controlled datacenters operational for the full fiscal year. Numerator: cooling and humidification water; not EU all-functions total input. The zero-evaporation next-generation design is a separate claim.
Scope & caveats
Respondent-survey statistic, not an industry-weighted fleet average. The public claim does not provide a population-weighting method; use it as a dated survey benchmark and retain the sample and survey methodology when comparing it with a named facility or fleet.
2025 survey figure (n=681). Uptime's 2026 survey (published 2026-07-28; analysed 2026-08-06) reports two separately defined successors: 1.52 as the annual survey average and 1.36 on a capacity-weighted basis — the gap is the larger-facility advantage, not an improvement in the same population. Neither is a measured average of the world fleet. Same 2026 survey: modal installed-base rack density reached 11 kW (from 9 kW in 2025) — the installed base, not the AI-factory design point.
Plant redundancy, concurrent maintainability, and thermal ride-through
Heat-rejection plant must be sized not just for the worst climate bin but for the worst climate bin with a unit down for maintenance. Concurrent maintainability — the Tier-III-and-up property that any single component can be taken out of service for planned work without dropping below design load — drives N+1 (or N+2) on towers, dry coolers, pumps, and chillers, with isolation valves and headered piping so a cell can be drained and serviced while the rest carry the heat. The redundancy count is set by your maintenance philosophy and your tier commitment; the harder, AI-specific problem is the selected product's tested response after an unplanned loss.
This is where dense DLC breaks the old playbook: it can spend the thermal inertia you once counted on — stored cold water riding a chiller trip or utility blink while generators picked up — if the new temperature margin or participating inventory is smaller; the liquid itself has not lost its heat capacity (Chapter 5.12 derives the tested flow-loss transient). Lose flow and the junction response—throttle, controlled shutdown, emergency shutdown or trip—must be established from product-specific data and testing; do not infer a universal time from a slow-plant comparison.
Deep dive: why the chiller-deletion decision changes the redundancy picture
There is a tempting symmetry to deleting the chiller in a cold-climate warm-water plant: the bin-hour overlay shows zero compressor-hours, and the capex and standby-loss savings from deleting a machine that never runs are real. But the redundancy consequence is subtle and worth stating, because it is a fork people get wrong.
A chiller, even one that almost never runs, is a capacity backstop of last resort: it can hold the loop on a freak heat event that exceeds the design wet-bulb, and it can provide the small stored-cold buffer that helps ride-through. Delete it and your plant's worst-case capacity is exactly what the dry/adiabatic stage can deliver on the hottest hour in the climate record — so you must design that stage with margin for a warming climate and for the one-in-N-year event, and you lean harder on pump continuity and buffer volume for ride-through because there is no chiller-fed cold reserve. The right answer at a cold site is to delete the chiller when the alternative closes the required extreme and unavailable-equipment states — but to do it with a hardened free-cooling stage and an explicit ride-through design, not by simply removing the box and inheriting its hidden ride-through role unfilled. In marginal-temperate sites, a small trim chiller can be a heat-wave-and-ride-through insurance policy that costs less than a larger dry array, when its surviving duty, supporting power and transition response meet the same requirement. The decision looks like a capex question but is really a climate-risk and ride-through question.
Choose the rejection system from annual energy and water inputs plus the required hottest and unavailable-unit states. Efficient weather bins do not compensate for a capacity failure. Add rejection capacity or adopt an explicit heat-reduction state before committing the hall’s usable IT load.
Cite this chapter
Fehn, J. (2026). Heat Rejection: Chillers, Dry Coolers, Towers, Adiabatic & Economizers (Chapter 5.8). The Definitive Guide to AI Data Centers. https://aidatacenterguide.com/part-5-cooling-and-thermal-management/5-8-heat-rejection-chillers-dry-coolers-towers-adiabatic-and-economizers (accessed 2026-09-29).
@misc{aidc-5-8,
author = {Fehn, Jacob},
title = {Heat Rejection: Chillers, Dry Coolers, Towers, Adiabatic & Economizers (Chapter 5.8)},
howpublished = {The Definitive Guide to AI Data Centers},
year = {2026},
url = {https://aidatacenterguide.com/part-5-cooling-and-thermal-management/5-8-heat-rejection-chillers-dry-coolers-towers-adiabatic-and-economizers},
note = {Accessed 2026-09-29}
}