The Definitive Guide toAI Data Centers
Ask the GuideAboutAccount
Guide › Glossary › RDHx

RDHx · Rear-Door Heat Exchanger

A liquid-cooled rack door removing ~50-100 kW without piping liquid to the chips; a brownfield step toward full DLC.

A radiator-style door on the back of a rack that cools exhaust air with liquid before it enters the room.

Also written as: Rear-Door Heat Exchanger

Current numbers

~10–30 kW typical; to ~50 kW on current productpassive RDHx capacity per rack (server fans only, zero added fan power)as of 2026-09 · register ↗
up to 75 kW — Motivair ChilledDooractive RDHx capacity per rack — Motivair ChilledDoor rated to ~75 kW at 100% heat capture; verify entering-air and entering-water temperatures, airflow and pressure dropas of 2026-07 · register ↗
10–100 kWRDHx capacity per rack (passive ~10–30 kW typical, to ~50 kW on current product; active ~50–100 kW); ~$8–15k/rackas of 2026-04 · register ↗

← All terms