NVIDIA's Vera Rubin reference example uses about 41 °C facility water into the CDU to provide 45 °C rack coolant
~41 °C FWS -> 45 °C rack coolantobserved
| Value kind | observed — Reported measurements, counts, and specifications keep the precision and scope stated by their source; an exact specification is not treated as a range. |
|---|---|
| Scope | Published NVIDIA reference design point for the Vera Rubin POD, a shipping platform: a named FWS/CDU/TCS example, not a universal facility-loop standard and not a metered facility loop. Derive the site setpoint from the named rack's approved envelope and the CDU approach. |
| As of | 2026-03-16 |
| Source | NVIDIA · Reference facility-water and rack-coolant temperatures for Vera Rubin POD |
| Review | checking…review by 2026-09-23 · fast cadence |
| Recorded changes | last 2026-08-24 · 2 revisions tracked |
| Claim id | warm-water-facility-loop-target-nvidia-vera |