Vera Rubin NVL72 rack power — 188 kW (Max Q) / 228 kW (Max P) OEM TDP support; both above GB300 NVL72 (135 kW TDP / 155 kW peak). Size a hall position from the facility design basis, not from either operating profile
188 kW (Max Q) / 228 kW (Max P)observed
| Value kind | observed — Reported measurements, counts, and specifications keep the precision and scope stated by their source; an exact specification is not treated as a range. |
|---|---|
| Scope | Operating profiles from the OEM rack datasheet, which also ships 4 × 110 kW power shelves. Distinct from the facility design basis: NVIDIA's DSX Facilities Infrastructure Design Guide v2.0 (2026-08-19) provisions a 330 kW cabinet TDP for Vera Rubin NVL72. Size substrate, busway, pipe and CDU from the design basis; run energy and TCO models on Max Q / Max P. |
| Caveat | TrendForce (2026-06-25) independently put VR200 rack draw at ~225 kW, inside the OEM Max Q–Max P band. NVIDIA publishes no rack-power figure on the product page. |
| As of | 2026-08 |
| Source | Pegatron RA4803-72N3 datasheet |
| Review | checking…review by 2026-11-28 · standard cadence |
| Recorded changes | last 2026-08-31 · 4 revisions tracked |
| Claim id | vera-rubin-nvl72-rack-power-max-q-max-p |
Where the guide uses it
← Full numbers register — every date-stamped figure in the guide, with revision history.