nVent RDHX PRO active 800 mm rear door, rated capacity at 14 °C supply water and 24 °C supply air

78 kW at 14 °C water / 24 °C airobserved

Value kindobserved — Reported measurements, counts, and specifications keep the precision and scope stated by their source; an exact specification is not treated as a range.
CaveatDoor capacity depends on water temperature and airflow. The same active door is rated 44 kW at 24 °C water and 27 °C air, and its table assumes 6.0 m³/h of water and 10,000 m³/h of air for the 750–800 mm variant. Passive doors carry less and are rated per model: nVent's passive 800 mm RDHX PRO is 38 kW at 14 °C water/24 °C air and 34 kW at 24 °C/27 °C. The datasheet prints no publication day. Get an OEM quotation for the door, interfaces, CDU allocation and installation.
As ofnVent datasheet ©2025; checked 2026-10-14
SourcenVent RDHX PRO active, SCHROFF-SPEC-N00647-RDHXPRO-EN
Reviewchecking…review by 2027-04-01 · standard cadence
Recorded changeslast 2026-10-14 · 5 revisions tracked
Claim idrdhx-capacity-per-rack-passive-15-30-kw-active

Where the guide uses it

← Full numbers register — every date-stamped figure in the guide, with revision history.