Diablo 400 v0.7.0 contains conflicting ground-fault-detector requirements for its solid-midpoint option.

Solid midpoint: conflicting detector clausesobservedcontested

Value kindobserved — Reported measurements, counts, and specifications keep the precision and scope stated by their source; an exact specification is not treated as a range.
ScopeSection 8.1.4.1.1 requires per-output detection for both midpoint schemes; 8.1.4.2 calls it optional for solid grounding. Project case specifies detection pending written resolution; HRG includes voltage-balance detection.
CaveatInternal specification conflict; do not infer a universal exemption for solid grounding.
As of2026-03-01
SourceOCP, Diablo 400 v0.7.0, March 1, 2026; §8.1.4.1.1 p.20 and §8.1.4.2 p.21. · §8.1.4.1.1 p.20 and §8.1.4.2 p.21.
Reviewchecking…review by 2027-03-05 · standard cadence
Recorded changesnone recorded
Claim idpart4-diablo-ground-fault-detection