Diablo 400 v0.7.0 contains conflicting ground-fault-detector requirements for its solid-midpoint option.
Solid midpoint: conflicting detector clausesobservedcontested
| Value kind | observed — Reported measurements, counts, and specifications keep the precision and scope stated by their source; an exact specification is not treated as a range. |
|---|---|
| Scope | Section 8.1.4.1.1 requires per-output detection for both midpoint schemes; 8.1.4.2 calls it optional for solid grounding. Project case specifies detection pending written resolution; HRG includes voltage-balance detection. |
| Caveat | Internal specification conflict; do not infer a universal exemption for solid grounding. |
| As of | 2026-03-01 |
| Source | OCP, Diablo 400 v0.7.0, March 1, 2026; §8.1.4.1.1 p.20 and §8.1.4.2 p.21. · §8.1.4.1.1 p.20 and §8.1.4.2 p.21. |
| Review | checking…review by 2027-03-05 · standard cadence |
| Recorded changes | none recorded |
| Claim id | part4-diablo-ground-fault-detection |