Illustrative series plate margin

2.82 K second-component margin in the series casemodeled

Value kindmodeled — Interpret this value according to its displayed kind, scope, source, and as-of date.
ScopeAssume two identical 1.00 kW components, water at 35.0 °C, 2.00 L/min through each plate, density 1.00 kg/L, specific heat 4.18 kJ/(kg·K), combined junction-to-inlet resistance 0.0400 K/W at that flow, and 20.0 kPa loss per plate. Each junction limit is 85.0 °C with 5.0 K reserve. Connecting-pipe loss is excluded to isolate the topology choice. These are teaching inputs bounded by the thermal method in 5.1 and the selected plate curve that procurement must obtain.
As of2026-09
SourceGuide calculation from expressly assumed teaching inputs. Primary reference supplies method or equipment context, not evidence that this design was built or tested.
DerivationParallel routing needs 4.00 L/min at 20.0 kPa plate-path loss. Both junctions are 35.0 + 1,000 × 0.0400 = 75.0 °C, retaining 10.0 K. Series needs 2.00 L/min at 40.0 kPa; the first plate raises water temperature by 1.00 × 60/(2.00 × 4.18) = 7.18 K, so the second junction is 82.2 °C and retains only 2.82 K. Choose parallel to preserve the required reserve. Ideal plate-only hydraulic power is 1.33 W in either arrangement; pump efficiency and external losses decide electrical input. The series choice reverses at supply ≤85.0 − 5.0 − 40.0 − 7.18 = 32.8 °C, calculated without intermediate rounding. Colder supply spends rejection opportunity to avoid extra header flow. Alternatively, qualify a different component/plate duty. OCP’s cold-plate method keeps the coolant-inlet reference explicit; use 5.1 for the thermal method and 5.13 for the complete hydraulic selection.
Reviewchecking…cadence-derived review 2027-01-03 · standard cadence
Recorded changesnone recorded
Claim idp5-series-plate-margin

Where the guide uses it

Not quoted in a chapter yet; it is kept in the curated register.

← Full numbers register — every date-stamped figure in the guide, with revision history.