The Definitive Guide toAI Data Centers
Ask the GuideAboutAccount
Guide › Numbers register › Claim

NVIDIA DSX Facilities Infrastructure Design Guide v2.0 TCS design-flow criterion

At least 1.5 L/min per kWrecommendation

Value kindrecommendation — Recommendations are design guidance, not measured facts; validate them against the project boundary conditions.
ScopeDSX CDU and technology-loop design criterion. State the kW basis in the project schedule and separately meet each connected rack's approved flow, temperature and pressure envelope.
As of2026-08-19
SourceNVIDIA DSX Facilities Infrastructure reference design overview (Design Guide v2.0, 19 August 2026), mechanical gallery CDUs
Reviewchecking…review by 2027-02-19 · standard cadence
Recorded changeslast 2026-10-25
Claim idp5-dsx-tcs-design-flow

Where the guide uses it

Not quoted in a chapter yet; it is kept in the curated register.

← Full numbers register — every date-stamped figure in the guide, with revision history.