The Definitive Guide toAI Data Centers
Ask the GuideAboutAccount
Guide › Numbers register › Claim

Illustrative c5 low delta t capacity

209 kW at the assumed low-rise flow ceilingmodeled

Value kindmodeled — Interpret this value according to its displayed kind, scope, source, and as-of date.
ScopeUse 320 kW liquid IT duty, idealized water at 1.00 kg/L and 4.18 kJ/(kg·K), and the 10.0 K IT rise of 5.1. Assume an installed flow ceiling of 600 L/min and a useful rise reduced to 5.00 K at full heat. These inputs isolate the IT branch from the CDU auxiliary heat and illustrate the bypass/flow constraints described here.
As of2026-09
SourceGuide calculation from expressly assumed teaching inputs. Primary reference supplies method or equipment context, not evidence that this design was built or tested.
DerivationRequired flow at 10.0 K is 459 L/min; at 5.00 K it is 919 L/min. At 600 L/min the reduced rise carries only (600/60) × 4.18 × 5.00 = 209 kW, leaving a 111 kW shortfall. Restore useful ΔT or change the qualified flow path before adding IT load. The crossover at 600 L/min is 320/[(600/60) × 4.18] = 7.66 K. At half heat, however, 459 L/min and 5.00 K carry 160 kW and are consistent; the issue becomes part-load pump energy rather than a capacity failure. Use 5.1 for the balance and 5.13 for the pump/system curve, with the ASHRAE CDU rating boundary keeping internal heat separate.
Reviewchecking…cadence-derived review 2027-01-03 · standard cadence
Recorded changesnone recorded
Claim idp5-c5-low-delta-t-capacity

Where the guide uses it

Not quoted in a chapter yet; it is kept in the curated register.

← Full numbers register — every date-stamped figure in the guide, with revision history.