Illustrative c5 fluid release example

6.0 ppm assumed fresh-fill chloride: hold against <5.0 ppmmodeled

Value kindmodeled — Interpret this value according to its displayed kind, scope, source, and as-of date.
ScopeAssume a first-fill PG formulation approved for the complete wetted-material list. For this teaching procurement schedule adopt fresh-fluid chloride <5.0 ppm from Table 1 of the linked OCP PG guidance, and hypothetical certificate/lab inputs: correct product and lot, PG concentration 26.0% by volume, pH 8.7, chloride 6.0 ppm, clear appearance, and all other agreed fresh-fluid tests satisfactory. The concentration and pH are assumed inside this formulation’s accepted limits; they do not approve other formulations or alloys. No supplier certificate or sample result has actually been obtained.
As of2026-09
SourceGuide calculation from expressly assumed teaching inputs. Primary reference supplies method or equipment context, not evidence that this design was built or tested.
DerivationThe batch fails because 6.0 ppm is not below 5.0 ppm. Hold first fill, have the fluid supplier investigate the water/formulation source and supply or correct the batch, then obtain a conforming resample. The crossover is chloride strictly below 5.0 ppm; an exact 5.0 ppm result also fails the adopted “less than” criterion. Measurement uncertainty and the decision rule must be agreed before a real borderline result can be released. Do not substitute the looser in-service chloride limit from OCP Table 4 for this fresh-fluid decision. The fluid owner retains the formulation/lot, approved wetted list, sampling location, test method, units and acceptance criteria alongside the certificate and lab report. Establish the baseline at fill and resample after incompatible make-up, repairs or adverse trends; the supplier sets the ongoing analytical interval and additive corrections. OCP PG guidance, Tables 1 and 4 and §6.3 distinguishes fresh and operating fluid. This chapter owns the fluid envelope; 13.5 receives its release record and 14.5 executes the maintenance program.
Reviewchecking…cadence-derived review 2027-01-03 · standard cadence
Recorded changesnone recorded
Claim idp5-c5-fluid-release-example