guide water heat-balance result at a 10 K design rise per kilowatt of liquid-captured heat

~1.43 L/min/kWderived

Value kindderived — Derived values are guide calculations; their result is only as fixed as the stated inputs, scope, and method.
ScopeA guide physics result, not an OCP or OEM flow specification. Apply it only to liquid-captured heat and recalculate with the approved fluid properties, selected ΔT, pressure budget, and product operating envelope.
As of2025
SourceGuide heat-balance derivation using water properties at the declared design point
DerivationQ = ṁ·cp·ΔT. Using water-like properties at the declared point, 1 kW / (4.18 kJ/kg·K × 10 K) = 0.0239 kg/s ≈ 1.43 L/min. Recalculate for the approved fluid and operating temperature.