The Definitive Guide toAI Data Centers
Ask the GuideAboutAccount
Guide › Numbers register › Claim

Most data centers are Risk Category II; Risk Category IV applies when a data center supports designated critical functions or essential facilities, or when Category IV is voluntarily selected for greater resilience

RC II typical; IV if designatedobserved

Value kindobserved — Reported measurements, counts, and specifications keep the precision and scope stated by their source; an exact specification is not treated as a range.
ScopeFor structural seismic design, Risk Category IV has Ie = 1.5 versus Ie = 1.0 for Category II, but data-center use alone does not trigger Category IV.
As of2023
SourceNational Institute of Standards and Technology, NIST GCR 23-037 · Section 2.1.3.1, “New Data Centers,” p. 31; Section 3.3.3, p. 84
Reviewchecking…review by 2027-07-26 · slow cadence
Recorded changeslast 2026-07-14 · 2 revisions tracked
Claim idmission-critical-classification-under-asce-7-22

Where the guide uses it