NFPA 70E 2024 incident-energy-analysis accuracy review interval and result-affecting change trigger
5 yearsobserved
| Value kind | observed — Reported measurements, counts, and specifications keep the precision and scope stated by their source; an exact specification is not treated as a range. |
|---|---|
| Scope | Historical 2024 edition: review incident-energy analysis for accuracy at intervals not exceeding five years; update it for electrical-distribution changes that can affect its results. Select the employer’s governing edition before adopting the program. |
| As of | 2024 edition (issued 2023-04-23) |
| Source | NFPA, NFPA 70E Standard for Electrical Safety in the Workplace, 2024 edition (issued 2023-04-23, effective 2023-05-13), 130.5(G) Incident Energy Analysis Method: review for accuracy at intervals not exceeding five years and update for changes that can affect the results. · 130.5(G), Incident Energy Analysis Method, printed p. 70E–29 (PDF p. 32); 130.5(H) separately covers label data. |
| Review | checking…review by 2027-03-08 · standard cadence |
| Recorded changes | last 2026-09-16 · 2 revisions tracked |
| Claim id | max-interval-to-review-an-arc-flash-study-or-on |
Where the guide uses it
← Full numbers register — every date-stamped figure in the guide, with revision history.