Release the rack interface schedule only when every service fits — stated inputs
Rack A: 120 kW input = 100 kW liquid + 20 kW room air; coolant 40°C inlet, maximum 55°C return, 2.0 kg/s, cp 4.18 kJ/(kg·K). Hall: 132 kW input capacity, 120 kW liquid duty, 18 kW room air; rear service clearance 0.80 m vs 0.90 m required. Rack/network/manifold/bus ready weeks 9/11/10/12; test 2 weeks; need-by week 14.modeled