Close the rail loss and shelf transient on separate boundaries — stated inputs
Rail: 0.80 V at 2,000 A; hot path 20 µΩ; step 1,000 A in 1.0 µs; loop inductance 10 pH; incremental droop budget 40 mV. Shelf: output 120 kW, efficiency 96%, input limit 125 kW; extra load 20 kW for 10 ms; capacitor window 50→46 V.modeled
| Value kind | modeled — Interpret this value according to its displayed kind, scope, source, and as-of date. |
|---|---|
| Scope | Separate rail and shelf boundaries. Unsupported sensitivities and rationale are in the opening callout; Chapter 4.7 owns the interface. Ideal screens exclude component tolerance, aging and dynamic validation. |
| As of | 2026-09 |
| Source | Texas Instruments, power-management fundamentals — method reference; guide-authored hypothetical scenario September 8, 2026. No supplier quote or test measurement. |
| Derivation | Exact teaching assumptions chosen to expose the stated constraint and its reversal; not estimates of market prices or actual equipment. |
| Review | checking…review by 2027-03-08 · standard cadence |
| Recorded changes | last 2026-09-16 |
| Claim id | guide2-t29-7-12-inputs |