The Definitive Guide toAI Data Centers
Ask the GuideAboutAccount
Guide › Numbers register › Claim

NVIDIA GB200 NVL72 (QCT QoolRack reference) maximum liquid inlet and return temperatures

45 °C maximum liquid inlet; 65 °C maximum liquid return (separate limits)observed

Value kindobserved — Reported measurements, counts, and specifications keep the precision and scope stated by their source; an exact specification is not treated as a range.
ScopeExact QCT reference. The 45 °C liquid-inlet maximum and 65 °C liquid-return maximum are separate limits, not a prescribed 20 K operating rise. Select a supported operating point, approved fluid, liquid heat load, and design ΔT; ASHRAE W45 describes FWS supply capability, not this product's setpoint.
CaveatSeparate acceptance maxima, not a prescribed 20 K operating rise; do not attribute these limits to HPE without an HPE document that states them.
As of2025-04
SourceQCT, QoolRack Stand-Alone Advanced Liquid Cooling for NVIDIA GB200 NVL72 Systems · PDF p.3, 'NVIDIA GB200 NVL72 Specs': maximum liquid inlet 45 °C; maximum liquid return 65 °C
Reviewchecking…review by 2027-08-24 · slow cadence
Recorded changeslast 2026-08-24 · 3 revisions tracked
Claim idgb200-nvl72-dlc-coolant-envelope-rack-accepts-2

Where the guide uses it

← Full numbers register — every date-stamped figure in the guide, with revision history.