GB200 NVL72 coolant flow in vendor reference designs at roughly 12 °C rise

~110–140 L/min (vendor references at ~12 °C rise)observed

Value kindobserved — Reported measurements, counts, and specifications keep the precision and scope stated by their source; an exact specification is not treated as a range.
ScopeThe vendor-reference band is observed in QCT and nVent designs at roughly 12 °C rise. The guide's separate ~165–236 L/min water-property design-flow derivation uses a tighter 7–10 °C rise across ~115 kW; Clariant PG25 gives ~172–246 L/min at the same rise, roughly 4% more.
CaveatQCT ≤130 L/min and nVent ~138 L/min are vendor-reference operating points; using the separate water-property guide band requires the guide's 7–10 °C design rise, while Clariant PG25 at the same rise gives the slightly higher ~172–246 L/min band.
As of2025
SourceQCT QoolRack GB200 NVL72 reference (≤130 L/min); nVent (~138 L/min/rack) · QCT QoolRack PDF p.3: up to 130 L/min; nVent GB200 NVL72 CDU reference: approximately 138 L/min per rack
Reviewchecking…review by 2027-06-22 · slow cadence
Recorded changeslast 2026-08-22 · 4 revisions tracked
Claim idgb200-nvl72-coolant-acceptance-envelope-and