data-center load lost in the July 10 2024 N. Virginia 230 kV disturbance (six faults over 82 s; 60 sites, 25 substations) — later a driver of NERC's rare May 2026 Level 3 alert

~1,500 MWobserved

Value kindobserved — Reported measurements, counts, and specifications keep the precision and scope stated by their source; an exact specification is not treated as a range.
ScopeLoad loss as seen by the grid. NERC's incident review ('Load Details') found the affected data centers transferred their loads to backup power — static UPS, decentralized rack UPS, or DRUPS — in response to the disturbance. The figure is a loss of demand at the interconnection, not evidence that IT power was interrupted or that training jobs restarted.
CaveatThe approximately 1,500 MW is the total customer-side load reduction coincident with the six-fault sequence; NERC reports approximately 1,260 MW as the sustained drop at the third voltage depression. The NERC-investigated canonical case. A second, larger occurrence followed on 2026-07-22: ~3.8 GW dropped on a single normally-cleared Ashburn 230 kV fault (see companion key number). Two vintages of the same failure mode, not a replacement figure.
As of2024-07
SourceNERC Incident Review of the July 2024 event; NERC Level 3 Alert (May 2026)
Reviewchecking…review by 2027-05-01 · standard cadence
Recorded changeslast 2026-09-16 · 21 revisions tracked
Claim iddata-center-load-lost-in-the-july-10-2024-n