in-row cooler capacity per cooling unit (Liebert CRV CR032–CR050); kW per rack depends on unit-to-rack ratio, containment and air conditions
~30–50 kWobserved
| Value kind | observed — Reported measurements, counts, and specifications keep the precision and scope stated by their source; an exact specification is not treated as a range. |
|---|---|
| Scope | Vertiv publishes these as per-unit cooling capacities (CR032/CR035/CR040/CR050). Converting them into kW per rack requires the number of units serving the row, airflow distribution, containment, entering-air conditions and the redundancy case. The figure does not establish an equivalent close-coupled fan-wall rating. |
| As of | 2025 |
| Source | Vertiv · Model Specifications Overview; CR032, CR035, CR040 and CR050 models provide 32–50 kW |
| Review | checking…review by 2026-10-27 · standard cadence |
| Recorded changes | last 2026-08-24 · 2 revisions tracked |
| Claim id | active-in-row-cooler-capacity-per-rack |
Where the guide uses it
← Full numbers register — every date-stamped figure in the guide, with revision history.