Rack cooling feasibility

Test a rack and facility envelope using rack power, the named liquid/residual-air heat split, qualified airflow and rear-door conditions, rack water availability, room residual capacity, and the roadmap case. Rack kW alone never selects the technology.

ScenarioNVIDIA GB200 NVL72 · 56 active / 72 installed GPUs · 0.13 MW IT · $5M programguide defaults (asof 2026-07)Edit the shared scenario →

Rack cooling feasibility

direct liquid cooling with air removal of the declared residual heat is feasible
Current liquid / residual-air split114.8 / 17.2 kW
Future residual-air load17.2 kW vs 20 kW limit

This is a preliminary envelope screen, not equipment qualification. Rack kW is one input alongside component heat flux, the named OEM heat split, airflow/inlet limits, supported TCS/FWS or entering-water conditions, room residual rejection, climate, serviceability, redundancy, and the refresh tail. Use product capacity only at its stated air/water temperatures, flow, pressure, fan state, containment, and heat-capture target → Ch 5.4.

These are transparent screening estimates, not final designs, financial advice, or project approvals. Replace every default with current project data and have the responsible project authorities validate the result. You can save, share a permalink, or export to CSV; see the full calculator suite.