Calculators › Rack cooling check

Rack cooling check

Find which cooling path carries a rack today and at your roadmap rack: air, air with a rear door, or direct liquid with room air or a rear door. Enter rack power, the rack maker's liquid share, the room's air capacity per rack, any rear door and your hottest-day facility water; get the residual air heat, the CDU flow at OCP's 1.25–2.0 L/min per kW, and the coolant temperature at the rack.

ScenarioNVIDIA GB300 NVL72 · 56 active / 72 installed GPUs · 1 racks · 0.14 MW IT · $9M programguide defaults (as of 2026-09)Edit your project assumptions →

Rack cooling check

Direct liquid + room air carries this 135 kW rack
Which cooling path carries the rack, today and at the roadmap rack
PathToday (135 kW)Roadmap (228 kW)
Air onlyNot applicable: 121.5 kW of this rack's heat must go to liquidNot applicable: 205.2 kW of this rack's heat must go to liquid
Air + rear doorNot applicable: 121.5 kW of this rack's heat must go to liquidNot applicable: 205.2 kW of this rack's heat must go to liquid
Direct liquid + room airWorks: liquid 121.5 kW, room 13.5 kW of its 20 kWFails: residual air 22.8 kW exceeds the room's 20 kW
Direct liquid + rear doorNot applicable: no rear door enteredNot applicable: no rear door entered
Heat to liquid / to room air, today121.5 / 13.5 kW
CDU flow for the liquid share at OCP's 1.25–2.0 L/min per kW152–243 L/min per rack
Coolant reaching the rack (facility water + CDU approach)35 °C against the rack's 45 °C limit
Roadmap rackNothing carries the 228 kW roadmap rack: residual air 22.8 kW exceeds the room's 20 kW

How this works: liquid heat is rack power times the liquid share, and the room's air takes the rest, through a rear door if you have one. The coolant reaching the rack is the facility water plus the CDU approach, and it must not be warmer than the rack allows → Ch 5.6. Flow uses OCP's PG25 guideline of 1.25–2.0 L/min per kW of liquid heat, which keeps the coolant rise near 7.5–12 °C → Ch 5.11. This is a screen: before you buy, get the rack maker's flow, pressure and fluid limits and check the room's airflow at the rack → Ch 5.4, Ch 5.3.

Worked decision — stated assumptions

All ledger inputs are assumed teaching values chosen to exercise this chapter’s method; they are not market quotes, OEM performance claims or operating records. Arithmetic uses the full entered precision.

Assumed inputs
InputValue
Rack power132 kW/rack
Heat captured to liquid87 % of rack heat
Room air capacity per rack20 kW/rack
Rear-door capacity0 kW/rack
Facility water to the CDU, hottest day30 °C
CDU approach5 K
Warmest coolant the rack accepts45 °C
Roadmap rack power132 kW/rack
Roadmap heat captured to liquid87 % of rack heat

Decide whether a GB200 NVL72-class rack fits this hall. Assume 132 kW per rack with 87% of the heat going to liquid (HPE's split), a room that can take 20 kW of air per rack, 30 °C facility water on the hottest day, a CDU with a 5 K approach and a rack that accepts coolant up to 45 °C. Liquid heat is 132 × 0.87 = 114.84 kW, and the room takes the other 17.16 kW, inside its 20 kW. The coolant reaches the rack at 30 + 5 = 35 °C, under the 45 °C limit, so direct liquid with room air works. At OCP's 1.25–2.0 L/min per kW, the CDU must deliver about 144–230 L/min to this rack.

Raise the hottest-day facility water to 41 °C: the coolant arrives at 46 °C and the liquid path fails. The crossover is 40 °C facility water at a 5 K approach; a CDU with a 3 K approach moves it to 42 °C. Get the rack maker's flow curve and pressure limits before you order.

Primary method: ASHRAE Handbook (2023), Applications ch. 20 — thermal paths and CDUs. Method and handoff: Chapter 5.6 — CDUs & the Secondary Loop.

These are transparent screening estimates, not final designs, financial advice, or project approvals. Replace every default with current project data and have the responsible project authorities validate the result. You can save, share a permalink, or export to CSV; see the full calculator suite.